Terminal
Number
10
0-10 VDC or 4-20 mA
Analog Output Reference
11
Regulator Common
7-10
Table 7.8 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Description
Wiring Analog Outputs
Parameters/Wiring Connections
The setting of parameter P.012 selects the terminal strip
analog output source (either speed or torque). Jumper J17
must also be set. See figure 2.13.
The 4-20mA current selection requires a power supply for
operation. The power can be sourced from the encoder
supply, terminal 4 (15VDC), or from an external 15V power
supply. Note that the maximum supply current from terminal
4 is 250mA (encoder and current source) at 15V.
On the 1-60 HP and 200-400 HP Regulator boards, terminals
9 and 11 are internally connected.
Load
(Meter or Analog Input)
Connection to the negative side of the
power supply is only required
when an external 15V power supply is used.
GV3000/SE AC Drive Hardware Reference, Version 6.06
Terminal
Strip
+
-
+
-
+
-