Wiring the Regulator Board Terminal Strip
This chapter describes how to wire the Regulator board terminal strip for stop,
encoder feedback, and remote control signals.
The signals available through the terminal strip are shown in tables 7.1 to 7.7 and
figures 7.1 and 7.2. Table 7.8 provides additional information.
Note that when the Control Source parameter (P.000) is set to remote (rE), the drive
will be controlled by the signals connected to the terminal strip. Refer to the
GV3000/SE Software Start-Up and Reference manual for more information on how
parameter P.000 is used to specify where the drive is controlled from.
Terminal #
1
Transmit (Tx)
2
Receive (Rx)
3
Regulator Common
Notes: The RS-232 terminals should only be used when the RS-232 communication
port (J8) or an Operator Interface Module (OIM) is not being used, as all three devices
use the same transmit/receive lines.
Terminal #
4
+15 VDC
5
Phase A
6
Phase A Not
7
Phase B
8
Phase B Not
9
Regulator Common
Notes: An encoder feedback device must be installed if FVC regulation is used.
Wiring the Regulator Board
Table 7.1 – RS-232 Connections (Terminals 1-3)
Table 7.2 – Encoder Connections (Terminals 4-9)
C
HAPTER
Terminal Strip
Signal
Signal
7
7-1