6-2
ATTENTION: Do not route signal and control wiring with power wiring in
the same conduit. This can cause interference with drive operation.
!
Failure to observe these precautions could result in damage to, or
destruction of, the equipment
ATTENTION: Unused wires in conduit must be grounded at both ends
to avoid a possible shock hazard caused by induced voltages. Also, if a
drive sharing a conduit is being serviced or installed, all drives using this
conduit should be disabled to eliminate the possible shock hazard from
cross-coupled motor leads. Failure to observe these precautions could
result in bodily injury.
Step 2. Connect the three-phase AC output power motor leads to the appropriate
output terminals.
On 1-60 HP drives, connect the motor leads to terminals U/T1, V/T2, W/T3
on the power terminal strip.
On 60-150 HP drives, connect the motor leads to terminals U, V, and W.
On 200-400 HP drives, connect the motor leads to terminals U/T1, V/T2, and
W/T3.
Step 3. Tighten the three-phase AC output power terminals to the proper torque
according to drive type as shown in table 5.2.
GV3000/SE AC Drive Hardware Reference, Version 6.06