Chapter
4
socket-outlet is installed near the equipment and is easily accessible.
4.3.1.2
BATTERY IMPLEMENTATION
Alcatel-Lucent OmniPCX Office Communication Server is supplied with one or more integrated
batteries; they are mounted and fixed with a solid bar on the rear plate.
Caution:
Alcatel-Lucent OmniPCX Office Compact Edition does not have integrated batteries.
4.3.1.2.1 Battery switch
The batteries are disconnected during transport using a switch soldered onto the power supply
board. When the mains cable is inserted in the socket, the switch is closed by a lever
incorporated in the mains socket.
4.3.1.2.2 Battery fuse
The battery fuse is located on the board and requires the back panel to be dismantled to gain
access. It has the following characteristics:
-
Rack1 and Rack3: 6.3 A fast, low cutoff (F 6.3 AL/250 V).
-
Rack2: 10 A fast, low cutoff (F 10 AL/250 V)

4.3.1.2.3 Battery replacement

Refer to the Maintenance form in the manual.
4.3.1.3
CONNECTING AN EXTERNAL BATTERY UNIT
Alcatel-Lucent OmniPCX Office Communication Server hardware units (L, M, S and
Alcatel-Lucent OmniPCX Office Compact Edition) can be powered by external batteries. The
use of external batteries is an alternative to the UPS solution. It ensures that the
Alcatel-Lucent OmniPCX Office Communication Server systems are backed up. This solution
offers a maximum autonomy of 8 hours.
4.3.1.3.1 Alcatel-Lucent OmniPCX Office Communication Server units that accept
external batteries
The following units can be powered by external batteries:
Unit (with power supply)
Unit Alcatel-Lucent OmniPCX Office Compact Edition
Unit S (Small) with 110-230V power supply
Unit M (Medium) with 230V power supply
Unit M (Medium) with 110V power supply
Unit L (Large) with 230V power supply
Unit L (Large) with 110V power supply
Before using external batteries, first remove any internal batteries installed in the unit
(supplied in the S, M and L units by default).
4.3.1.3.2 Hardware
4-20
Reference
3EH 08271 AA
3EH 08227 AA
3EH 08228 AA
3EH 08228 AB
3EH 08229 AA
3EH 08229 AB