B.2 Parameter Table
No.
Name
DC Injection
Braking Time/DC
b2-03
Excitation Time at
Start
DC Injection
b2-04
Braking Time at
Stop
u

C: Tuning

C parameters are used to adjust the acceleration and deceleration times, S-curves, slip and torque compensation functions
and carrier frequency selections.
No.
Name
C1-01
Acceleration Time
<22>
1
C1-02
Deceleration Time
<22>
1
C1-03
Acceleration Time
<22>
2
C1-04
Deceleration Time
<22>
2
C1-09 Fast-Stop Time
S-Curve
C2-01
Characteristic at
Accel Start
S-Curve
C2-02
Characteristic at
Accel End
S-Curve
C2-03
Characteristic at
Decel Start
S-Curve
C2-04
Characteristic at
Decel End
C3-01
Slip Compensation
<22>
Gain
Slip Compensation
C3-02
Primary Delay
Time
Torque
C4-01
Compensation
<22>
Gain
C6-01 Normal/Heavy
Duty Selection
172
Description
Sets DC Injection Braking time at start. Disabled when set to 0.00
seconds.
Sets DC Injection Braking time at stop.
When b1-03 = 0, this parameter sets the amount of DC Injection
time applied to the motor at the end of the decel ramp. Disabled
when set to 0.00.
Description
C1: Acceleration and Deceleration Times
Use C1 parameters to configure motor acceleration and deceleration.
Sets the time to accelerate from 0 to maximum frequency.
Sets the time to decelerate from maximum frequency to 0.
Sets the time to accelerate from 0 to maximum frequency when
Accel/Decel times 2 are selected by a digital input.
Sets the time to decelerate from maximum frequency to 0 when
Accel/Decel times 2 are selected by a digital input.
Sets the time to decelerate from maximum frequency to 0 for the
multi-function input fast-stop function.
Note: This parameter is also used by selecting "Fast-Stop" as a Stop
Method when a fault is detected.
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
The S-curve can be controlled in the four points shown below.
Run
ON
OFF
command
Output
frequency
C2-02
C2-03
C2-01
S-curve is used to further soften the starting and stopping ramp. The
longer the S-curve time, the softer the starting and stopping ramp.
Use C3 parameters to configure the slip compensation function.
Sets the slip compensation gain. Decides for what amount the output
frequency is boosted in order to compensate the slip.
Note: Adjustment is not normally required.
Adjusts the slip compensation function delay time.
Decrease the setting when the slip compensation response is too
slow, increase it when the speed is not stable.
Use C4 parameters to configure Torque Compensation function.
Sets the gain for the automatic torque (voltage) boost function and
helps to produce better starting torque.
Increase this setting when using a long motor cable or when the
motor is significantly smaller than the drive capacity.
Decrease this setting when motor oscillation occurs. Set the value
so that the current at low speed does not exceeds the drive rated
current.
Use C6 parameters to configure the carrier frequency drive settings.
Selects the load rating for the drive.
0: Heavy Duty (HD) for constant torque applications.
1: Normal Duty (ND) for variable torque applications.
This setting affects the Rated output current and overload tolerance
of the drive.
C2-04
Time
C3: Slip Compensation
C4: Torque Compensation
C6: Carrier Frequency
Range
Def.
Mode
0.00 to
0.00 s
O
10.00
0.00 to
0.50 s
O
10.00
Range
Def.
Mode
S
S
O
0.0 to
10.0 s
6000.0
O
O
0.00 to
0.20 s
O
10.00
0.00 to
0.20 s
O
10.00
0.00 to
0.20 s
O
10.00
0.00 to
0.00 s
O
10.00
0.0 to 2.5
0.0
O
0 to 10000 2000
O
ms
0.00 to
1.00
O
2.50
0, 1
0
S
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Addr.
Pg.
Hex
18B
76
18C
76
Addr.
Pg.
Hex
200
77
201
77
202
77
203
77
208
77
20B
78
20C
78
20D
78
20E
78
20F
78
210
78
215
78
223
79

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jza j1000

Table of Contents