Drive Specifications; Drive Specifications - Omron JZA User Manual

Compact general purpose inverter 200 v class three-phase input 0.1 to 0.4 kw 200 v class single-phase input 0.1 to 1.5 kw 400 v class three-phase input 0.2 to 4.0 kw
Hide thumbs Also See for JZA:
Table of Contents

Advertisement

A.4 Drive Specifications
Note: For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.
Item
Frequency Setting Resolution
Output Frequency Calculation
Control
Characteristics
Momentary Power Loss Ride-Thru
Protection Functions
Heatsink Overheat Protection
Braking Resistor Overheat Protection Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Cooling Fan Failure Protection
Environment
Protective Enclosure
SIEP C710606 33A OYMC AC Drive – J1000 User Manual
Control Method
Frequency Control Range
Frequency Accuracy
Resolution
Frequency Setting Signal
Starting Torque
Speed Control Range
Accel/Decel Time
Braking Torque
V/f Characteristics
Functions
Motor Protection
Overcurrent Protection
Overload Protection
Low Voltage Protection
Stall Prevention
Ground Protection
DC Bus Charge LED
Storage/Installation Area
Ambient Temperature
Humidity
Storage Temperature
Altitude
Shock, Impact
Surrounding Area
Orientation
V/f Control
0.01 to 400 Hz
Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)
Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C)
Digital inputs: 0.01 Hz
Analog inputs: 1/1000 of maximum output frequency
20
1/2
x Maximum output frequency (E1–04)
Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA
(250 Ω)
150%/3 Hz
1: 20~40
0.00 to 6000.0 s (allows four separate settings for accel and decel)
Instantaneous Average Decel Torque
over 100%, 1.5 kW: over 50%, 2.2 kW and above: over 20%
Continuous Regen Torque: 20%,
125% with a Braking Resistor Unit
resistor.
User-set, programmable.
• Momentary Power Loss Ride-Thru
• Speed Search
• Multi-Step Speed (9 steps max)
• Accel/Decel Time Switch
• S-Curve Accel/Decel
• 3-Wire Sequence
• Cooling Fan ON/OFF
• Slip Compensation
• Torque Compensation
• Jump Frequencies (reference dead band)
• Frequency Reference Upper/Lower Limit
• DC Injection Braking (start and stop)
• Overexcitation Braking
• Fault Reset
Motor overheat protection via output current sensor
Drives stops when output exceeds 200% of the rated current (Heavy Duty)
A stop command will be entered after operating at 150% for 60 s (Heavy
<3>
Duty)
Drive stops when DC bus voltage falls below the levels indicated:
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350
V (3-phase 380 V)
Stops after 15 ms
Protected by thermistor
During acceleration and during run: Separate settings for each type of stall
prevention determine the current level at which stall prevention is triggered.
During deceleration: Select, enable/disable.
Circuit protection ("fan-lock" sensor)
<4>
Electronic circuit protection
Remains lit until DC bus voltage falls below 50 V
Indoors
-10 to +50 °C (IP20/Open-Chassis)
95% RH or less with no condensation
-20 to +60 °C allowed for short-term transport of the product
1000 m or less
2
10 to 20 Hz: 9.8 m/s
2
20 to 55 Hz: 5.9 m/s
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Install the drive vertically to maintain maximum cooling effects
IP20/Open-Chassis
A.4 Drive Specifications
Specification
<1>
: 0.1/0.2 kW: over 150%, 0.4/0.75 kW:
<2>
: (10% ED) 10 s with an internal braking
A
165