3 Mounting
A
A
H
16
Forms A, H, UO, Q, V may only be used in pressure-free media.
- To ensure their overall accuracy, the thermostats must only be used in con-
junction with the pockets supplied by the factory.
- Fitting several probes into a common pocket is only permitted with 2 or 3
cylindrical probes 6 mm dia. and pockets 15 x 0.75 mm.
- When fitting 2 probes into a pocket, the factory-supplied spring clip must
be fitted in the pocket.
- When used in air, the temperature probe must be used without a pocket.
The temperature probe (2) must be immersed in the medium for its entire
length, otherwise there will be appreciable deviations from the switching point.
In the case of probe mountings U, US, UH and UO, the temperature probe is
secured in the pocket with a clip (1).
(1)
(2)