5 Settings
5.3
Limit locking
5.4
Self-monitoring
5.4.1 Response to a measurement system fracture
H
A fracture of the measurement system (leakage), will cause the circuit on the
STB to open permanently and, in addition, the microswitch is locked out.
5.4.2 Response to low temperature
H
When the temperature falls below the minimum probe temperature -10°C (on
the STB), the circuit opens automatically.
When the temperature goes above the minimum probe temperature, the STB
must be reset manually.
20
( 1 ) Cover
( 2 ) Lead-sealable screw
Chapter 5.2 "Resetting the protection temperature limiter (STB)", page 19.
( 1 )
( 2 )