Vent Terminal Clearances - Jøtul GF 400 DV Sebago Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Horizontal Termination Clearance
Figure 19. Vent Terminal Clearances - National Fuel Gas Code.
A A A A A = Clearance above grade, veranda, porch , deck, or
balcony : 12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
B B B B B = Clearance to window or door that may be opened:
**Min.
**Min.
9 inches
9 inches, , , , , U U U U U.S .S .S .S .S. . . . . / / / / / *12 inches (30 cm) C
9 inches
*12 inches (30 cm) C
*12 inches (30 cm) C
**Min.
**Min. 9 inches
**Min.
9 inches
*12 inches (30 cm) CAN.
*12 inches (30 cm) C
We recommend 12in. minimum to prevent condensa-
tion on the window.
C C C C C = Clearance to permanently closed window:
**Min.
**Min.
**Min.
**Min. 9 inches
**Min.
9 inches
9 inches
9 inches
9 inches, , , , , U U U U U.S .S .S .S .S. . . . . / / / / / *12 inches (30 cm) C
*12 inches (30 cm) C
*12 inches (30 cm) C
*12 inches (30 cm) CAN
*12 inches (30 cm) C
We recommend 12 in. minimum to prevent condensa-
tion on the window.
D D D D D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(4 (4 (4 (4 (46 cm) minimum.
6 cm) minimum.
6 cm) minimum.
6 cm) minimum.
6 cm) minimum.
E E E E E = Clearance to unventilated soffit: 12 inches (4
minimum.
minimum.
minimum.
minimum.
minimum.
F F F F F = Clearance to outside corner: **Min.
inches (30 cm) C
inches (30 cm) C
inches (30 cm) CAN.
inches (30 cm) C
inches (30 cm) C
AN. We strongly recommend 12 inches,
AN.
AN.
AN.
particularly where windy conditions pevail.
G =
G =
G =
G =
G = Clearance to inside corner: ** Min.
inches (30 cm) C
inches (30 cm) C
AN.
AN.
inches (30 cm) CAN.
inches (30 cm) C
inches (30 cm) C
AN.
AN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H =
H = *Not to be installed within 15 f
H =
H =
H =
within 15 f
within 15 f
within 15 feet
within 15 f
meter/regulator assembly within 3 f
horizontally from the center-line of the regulator.
I I I I I = Clearance to service regulator vent outlet:
3 feet
3 f
3 f
eet
eet
eet (91 cm) minimum.
(91 cm) minimum.
(91 cm) minimum.
(91 cm) minimum.
3 f
3 f
eet
(91 cm) minimum.
J J J J J = Clearance to nonmechanical air supply inlet to building
or the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
12 inches (30 cm) minimum.
K K K K K = Clearance to a mechanical air supply inlet:
**Min.
**Min.
3 f
3 f
eet
eet
(91 cm) abov v v v v e if within 10 f
(91 cm) abo
(91 cm) abo
**Min. 3 f
**Min.
**Min.
3 feet
3 f
eet
eet (91 cm) abo
(91 cm) abo
tally, , , , , U U U U U.S .S .S .S .S. . . . . / *6 f
tally
tally
/ *6 f
/ *6 f
/ *6 feet
eet (1.83 m) minimum / C
eet
eet
(1.83 m) minimum / C
(1.83 m) minimum / C
(1.83 m) minimum / CAN
tally
tally
/ *6 f
eet
(1.83 m) minimum / C
AN.
AN.
AN.
AN.
AN
AN
AN
AN
18 inches
18 inches
18 inches
18 inches
12 inches (4
12 inches (4
6 cm)
6 cm)
12 inches (4
12 inches (46 cm)
6 cm)
6 cm)
**Min.
**Min.
**Min.
**Min. 9 inches
9 inches
9 inches, , , , , U U U U U.S .S .S .S .S. . . . . / / / / / *12
9 inches
9 inches
*12
*12
*12
*12
** Min.
** Min.
6 inches
6 inches, , , , , U U U U U.S .S .S .S .S. . . . . / / / / / *12
6 inches
*12
*12
** Min.
** Min. 6 inches
6 inches
*12
*12
eet
eet
eet
eet (4 (4 (4 (4 (4.5 m) abo
.5 m) abov v v v v e e e e e a
.5 m) abo
.5 m) abo
.5 m) abo
within 3 f
within 3 feet
within 3 f
within 3 f
eet
eet
eet
eet (90 cm)
(90 cm)
(90 cm)
(90 cm)
(90 cm)
e if within 10 f
e if within 10 f
eet
eet
horiz
horiz
on-
on-
e if within 10 f
e if within 10 feet
eet horiz
eet
horizon-
horiz
on-
on-
AN
AN
AN
AN
L =
L =
L =
L =
L =
Clearance above paved sidewalk or a paved driveway
1 1 1 1 1
located on public property: 7 feet (2.1 m) min. . . . .
M M M M M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum.
* In accordance with CSA B149 Installation Codes.
** In accordance with the current ANSI Z223.1/NFFPA 54,
National Fuel Gas Code. Note: Local Codes and Regulations may
require different clearances.
1 1 1 1 1
A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.
2 2 2 2 2
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
2 1/2”
12 ”
64 mm
305
3”
mm
76 mm
Figure 20. Termination Clearance to overhangs
2
15