Co-Linear Termination - Jøtul GF 400 DV Sebago Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Co-linear Vent Installation
This appliance may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appli-
ance in cold climate situations, as well as simplify the
vent installation. See fig. 13.
These installation requirements must be followed:
1. Use the guidelines for Co-linear Vent Termination
appropriate for your gas type on pages 10 - 11.
1. Prior to the installation the chimney flue must be
thoroughly cleaned and inspected by a qualified
chimney service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
4. No appliance can be installed into a chimney flue
serving any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND 6 FEET
BEYOND THE DAMPER AREA OF THE FIREPLACE.
6. If the intake flex duct does not extend the full length
of the chimney and connect to both the unit and the
termination cap, A METAL BLOCK OFF PLATE MUST BE
CONSTRUCTED AND INSTALLED ABOVE THE UNIT
PRIOR TO THE END OF THE INTAKE FLEX AND MUST
COMPLETELY SEAL THE CHIMNEY FLUE FROM THE
ROOM.
Consult with the local code authority having jurisdic-
tion before proceeding with this type of installation.
Refer to the vent manufacturer's instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUCTIONS
PROVIDED WITH EACH VENT COMPONENT.
12
Exhaust Gas
Max. Co-linear
Height - 35 ft.
(10.66 m)
Min. Co-linear
Height - 10 ft.
(3.05 m)
The chimney
must be sealed
off from the
room by a steel
plate at the
damper area.
Figure 13. Co-linear Adaptor installed through a masonry
chimney. Components shown may differ somewhat from
manufacturer to manufacturer.
Figure 14. Simpson Dura-Vent #923GCL Co-linear Adaptor is
shown - other manufacturer's components may differ.
Subtract 2 1/4" for Short Legs.
High Wind Cap
Intake Air
The Air
Intake Flex
pipe must
extend
beyond the
damper.
Dual 3"Flex
Liners
Max. offset
24"
(609 mm)
29"
to top of
Co-linear
25 1/2"
Adapter.
to center
of flue collar

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents