Installation (for qualified installers only)

Vent Requirements

Travis Industries manufactures a
vent kit specifically for this insert
(sku 96200330). It includes 30'
(10M) of vent, hose clamps, and a
prairie cap. The flashing on the cap
is 18" (458mm) by 18" (458mm).
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use its own separate vent system.
Make sure the exhaust pipe on the heater connects to the exhaust portion of the cap. The
illustrations below show how the flex liners should be attached.
The exhaust vent must reline the entire length of the chimney and terminate above the chimney top.
Be careful not to crimp or rupture the liner when bending it into chimney offsets.
When installed, the vent must meet all of the vent manufacturer's requirements.
Use the following vent:
3" UL 441 or 1777 Gas Liner for Exhaust, 3" UL 441 or 1777 Gas Liner for Air Inlet
Duravent 6-5/8" to 3" Co-Linear Adapter and Flashing (46DVA-Gk)
Duravent High-Wind Vertical Termination (46DVA-VCH) for high-wind applications or Prairie Cap

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1,800 M). In this testing we
have found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety
hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Exhaust
Exhaust
(3" dia.)
Max. Ht. 40' (12.2M)
Min. Ht. 8' (2.5M)
4140811
Inlet
Inlet
(3" dia.)
Max. 2'
(610mm)
offset
100-01340