Type 2 Valves - Mira DISCOVERY Installation And User Manual

Thermostatic mixer
Table of Contents

Advertisement

Application
The approved designations for Type 2 Valves are as follows:
Models
Mira Discovery
Important! The fitting of any flow regulator will invalidate TMV2 compliance
due to the minimum flow rate requirements. Do not fit flow regulators in TMV2
applications.
Conditions of use for Type 2 Valves
Operating Pressure
Range
Maximum Static
Pressure (bar)
Maintained Pressure,
Hot and Cold (bar)
Hot Supply
Temperature (°C)
Cold Supply
Temperature (°C)
Valves operating outside these conditions cannot be guaranteed to operate as

Type 2 Valves.

Recommended Outlet Temperatures
The BuildCert TMV scheme recommends the following set maximum mixed water
outlet temperatures for use in all premises:
44°C for bath fill, but see notes below;
41°C for showers;
41°C for washbasins;
38°C for bidets.
The mixed water temperatures must never exceed 46°C.
The maximum mixed water temperature can be 2°C above the recommended
maximum set outlet temperatures.
Note! 46°C is the maximum mixed water temperature from the bath tap. The
maximum temperature takes account of the allowable temperature tolerances
inherent in thermostatic mixing valves and temperature losses in metal baths.
It is not a safe bathing temperature for adults or children.
TYPE 2 VALVES
High Pressure
10
0.5 to 5
55 to 65
≤25
32
Designation
LP-S, HP-S
Low Pressure
10
0.1 to 1
55 to 65
≤25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents