(2) Low Voltage Directive
1) Our view of transistorized inverters for the Low Voltage Directive
Transistorized inverters are covered by the Low Voltage Directive (Standard to
conform to: EN50178).
2) Compliance
We have self-confirmed our inverters as products compliant to the Low Voltage
Directive and place the CE mark on the inverters.
3) Outline of instructions
* For the 400V class inverter, the rated input voltage range is three phase 380V to
415V 50Hz/60Hz.
* Do not use an earth leakage circuit breaker as an electric shock protector without
connecting the equipment to the earth. Connect the equipment to the earth securely.
* Wire the earth terminal independently. (Do not connect two or more cables to one
terminal.)
* Use the cable sizes on page 10 under the following conditions.
·
Ambient temperature: 40 ° C (104 ° F) maximum
·
Wire installation: On wall without ducts or conduits
If conditions are different from above, select appropriate wire according to
EN60204 ANNEX C TABLE 5.
* Use the no-fuse breaker and magnetic contactor which conform to the EN or IEC
Standard.
* Use the breaker of type B (breaker which can detect both AC and DC). If not,
provide double or enhanced insulation between the inverter and other equipment,
or put a transformer between the main power supply and inverter.
* Use the inverter under the conditions of overvoltage category II and contamination
level 2 or higher specified in IEC664.
* On the input and output of the inverter, use cables of the type and size set forth in
EN60204 Appendix C.
* The operating capacity of the relay outputs (terminal symbols A, B, C) should be
30VDC, 0.3A.
* Control circuit terminals on page 11 are safely isolated from the main circuit.
* Environment
Ambient Temperature
Ambient Humidity
Maximum Altitude
Details are given in the technical information "Low Voltage Directive Conformance
Guide" (BCN-A21041-203). Please contact your sales representative.
During operation
-10 ° C to +50 ° C
(-14 ° F to 122 ° F)
90% RH or less
1,000m
(3280.80 feet)
85
In storage
-20 ° C to +65 ° C
(-4 ° F to 149 ° F)
90% RH or less
1,000m
(3280.80 feet)
During
transportation
-20 ° C to +65 ° C
(-4 ° F to 149 ° F)
90% RH or less
10,000m
(32808.40 feet)