Mitsubishi Electric FR-S500 Series Instruction Manual page 64

Transistorized inverter
Hide thumbs Also See for FR-S500 Series:
Table of Contents

Advertisement

Parameter for manufacturer setting
Parameter
Indication
b1
(560)
b2
(561)
Calibration parameter
Parameter
Indication
C1
AM terminal calibration
(901)
C2
Frequency setting
voltage bias frequency
(902)
C3
Frequency setting
voltage bias
(902)
C4
Frequency setting
voltage gain
(903)
C5
Frequency setting
current bias frequency
(904)
C6
Frequency setting
current bias
(904)
C7
Frequency setting
current gain
(905)
C8
(269)
CLr
Parameter clear
ECL
Alarm history clear
*Settings may differ because of calibration parameters.
Name
Parameter for manufacturer setting. Do not set.
Name
You can calibrate the indicator connected
to across terminals AM-5.
You can set as desired the magnitude
(slope) of the output frequency to the
external frequency setting voltage signal
(0 to 5V or 0 to 10V). (Bias frequency)
0 to 60Hz
Used to adjust the analog voltage value of
the frequency set in calibration parameter
C2. (Bias %)
0 to 300%
Used to adjust the analog voltage value of
the frequency set in Pr. 38. (Gain %)
0 to 300%
You can set as desired the magnitude
(slope) of the output frequency to the
external frequency setting current signal
(4 to 20mA).
0 to 60Hz
Used to adjust the analog current value of
the frequency set in calibration parameter
C5. (Bias %)
0 to 300%
Used to adjust the analog current value of
the frequency set in Pr. 39 (Gain %)
0 to 300%
0: Not executed
1: Initialization of parameters other than
calibration values (parameter clear)
10: Initialization of parameters including
calibration values (all clear)
0: Not cleared
1: Alarm history clear
59
Extended function parameter list
Description
Description
Refer to page 8
Factory
Setting
Factory
Setting
0Hz
0%*
96%*
0Hz
20%*
100%*
6
0
0