Mitsubishi Electric FR-S500 Series Instruction Manual page 45

Transistorized inverter
Hide thumbs Also See for FR-S500 Series:
Table of Contents

Advertisement

Changing the output frequency setting of the frequency setting
potentiometer (bias and gain of frequency setting voltage (current))
Changing example
POINT
•Pr. 38 is an extended function parameter. Pr. 30 must be set to "1".
(Refer to page 48.)
•Change Pr. 38 "frequency setting voltage gain frequency" to 50Hz.
(1) -1) Changing the highest frequency (0 to 5V input)
Operation
1.
Confirm the RUN indication
and operation mode indication.
The inverter must be at a stop.
The inverter must be in
the PU operation mode.
2.
Press the
to choose
MODE
the parameter setting mode.
3.
Turn the
until
Pr. 38 "frequency setting
voltage gain frequency" appears.
Pr. 30 must be set to "1"
(Refer to steps 3 to 6 on
page 48
for the parameter
setting method.)
4.
Press the
to display
SET
the currently set value.(60Hz)
5.
Turn the
to change it to
"50.0".(50Hz)
6.
Press the
to set
SET
the value.
By turning the
Press the
Press the
The monitor/frequency setting indication cannot be changed to just
50Hz ...Why?
The calibration parameter C4 "frequency setting voltage gain" value must
be set. (Refer to page 42.)
REMARKS
To change the value to more than 60Hz, Pr. 1 "maximum frequency" must be set to more than
60Hz.
When you want to use the 0 to 5VDC input frequency
setting potentiometer to change the 5V-time frequency
from 60Hz (factory setting) to 50Hz.
PU
(Press the
)
EXT
MODE
SET
SET
Flicker...Parameter setting complete!!
, you can read another parameter.
to show the setting again.
SET
twice to show the next parameter.
SET
40
Display
RUN
PU
EXT
The parameter
number read
previously
appears.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents