Mitsubishi Electric FR-S500 Series Instruction Manual page 39

Transistorized inverter
Hide thumbs Also See for FR-S500 Series:
Table of Contents

Advertisement

Operation by the start command of the terminal block
(external operation)
4.4.4
Perform frequency setting by analog (current input)
POINT
Switch terminal STF(STR)-SD on to give a start command.
Assign the AU signal to any of the terminal RH, RM, RL, or STR and turn on the
AU signal. (Refer to page 26)
Set "2" (external operation mode) in Pr. 79 "Operation mode selection".
[Connection diagram]
Forward rotation start
Reverse rotation start
1.
Power on
operation mode check
For the factory setting, the inverter operates
in the external operation mode [EXT] when
powering on. Check that the operation
command indication is [EXT]. If not displayed,
press
to change to the external [EXT] operation
mode. If the operation mode still does not change, set
Pr. 79 to change to the external operation mode.
(Refer to page 46)
2.
Start
Turn the start switch (STF or STR) on.
RUN of operation indication flickers.
CAUTION
When both the forward switch and reverse
switch are on, the inverter will not start.
Also, if both switches turn on while
running, the inverter decelerates to stop.
3.
Acceleration
Perform 20mA input.
The frequency value on the
indication increases according to
Pr. 7 "Acceleration time" until
60.0Hz is displayed.
Three-phase
AC power supply
AU signal
Output of the
adjustment meter
(4 to 20mADC)
Operation
constant speed
Inverter
R
S
T
STF
STR
AU
SD
4
( )
5( )
ON
Forward
rotation Reverse
rotation
ON
Output of the
adjustment meter
(4 to 20mADC)
34
U
Motor
V
W
Display
RUN
PU
EXT
RUN
Flickering
PU
EXT
RUN
PU
EXT