Extended function parameter list
Parameter
Indication
RL terminal function
60
selection
RM terminal function
61
selection
RH terminal function
62
selection
STR terminal function
63
selection
RUN terminal function
64
selection
A, B, C terminal
65
function selection
66
Retry selection
Number of retries at
67
alarm occurrence
Name
You can select the following input signals.
0: RL (multiple low-speed operation
command)
1: RM (multiple middle-speed operation
command)
2: RH (multiple high-speed operation
command)
3: RT (second function selection)
4: AU (current input selection)
5: STOP (start self-holding selection)
6: MRS (output stop)
7: OH (external thermal relay input)
8: REX (15 multi-speed selection)
9: JOG (jog operation selection)
10: RES (reset)
14: X14 (PID control valid terminal)
16: X16 (PU operation/external operation
switching)
- - -: STR (reverse rotation start (may be
You can select the following input signals.
0: RUN (inverter running)
1: SU (up-to-frequency)
3: OL (overload warning)
4: FU (output frequency detection)
11: RY (operation ready)
12: Y12 (output current detection)
13: Y13 (zero current detection)
14: FDN (PID lower limit signal)
15: FUP (PID upper limit signal)
16: RL (PID forward/reverse rotation
signal)
93: Y93 (current average value monitor
signal (can be assigned to the RUN
terminal only))
95: Y95 (maintenance timer alarm)
98: LF (minor failure output)
99: ABC (alarm output)
You can choose the retry alarm to be
activated when the protective function is
activated.
0: OC1 to 3, OV1 to 3, THM, THT, BE, GF,
OHT, OLT, PE, OPT
1: OC1 to 3, 2: OV1 to 3, 3: OC1 to 3, OV1
to 3
You can set the number of retries to be
made when the protective function is
activated.
0: No retry
1 to 10: Without alarm output during retry
101 to 110: With alarm output during retry
Description
assigned to only STR terminal))
operation
operation
54
Factory
Setting
0
1
2
- - -
0
99
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents