Mitsubishi Electric FR-S500 Series Instruction Manual page 17

Transistorized inverter
Hide thumbs Also See for FR-S500 Series:
Table of Contents

Advertisement

Control circuit
Symbol
Terminal Name
A
B
Alarm output
C
Inverter
RUN
running
Open collector
SE
common
Analog signal
AM
output
RS-485
——
connector
*1. Do not connect terminals SD and PC each other or to the ground.
For sink logic (factory setting), terminal SD acts as the common terminal of contact input.
For source logic, terminal PC acts as the common terminal of contact input. (Refer to the
separately available instruction manual (detailed) for switching method.)
*2. Low indicates that the open collector output transistor is on (conducts). High indicates
that the transistor is off (does not conduct).
*3. RL, RM, RH, RT, AU, STOP, MRS, OH, REX, JOG, RES, X14, X16, (STR) signal
selection (Refer to page 54.)
*4. RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL, Y93, Y95, LF, ABC signal selection
(Refer to page 54.)
*5. To be compliant with the European Directive (Low Voltage Directive), the operating
capacity of relay outputs (A, B, C) should be 30VDC 0.3A.
*6. Terminals SD, SE and 5 are isolated from each other. Do not ground.
Changeover contact output indicates
that the inverter protective function has
activated and the output stopped.
230VAC 0.3A, 30VDC 0.3A. Alarm:
discontinuity across B-C (continuity
across A-C), Normal: continuity across
B-C (discontinuity across A-C).(*5)
Switched low when the inverter output
frequency is equal to or higher than the
starting frequency (factory set to 0.5Hz
variable). Switched high during stop or
DC injection brake operation. (*2)
Permissible load 24VDC 0.1A (a
voltage drop is 3.4V maximum when
the signal is on)
Common terminal for inverter running terminal RUN. (*6)
The output signal across terminals AM-5 is factory set to about
5VDC at 60Hz and is proportional to the corresponding output
frequency.
Frequency permissible load current 1mA
Output signal 0 to 5VDC
Using the parameter unit connection cable (FR-CB201 to
205), the parameter unit (FR-PU04) can be connected.
Communication operation can be performed using RS-485.
For details of RS-485 communication, refer to the
separately available instruction manual (detailed).
12
Definition
The function of the
terminals changes
according to the
output terminal
function selection
(Pr. 64, Pr.65).
(*4)