6.3.2

Object request (network input SNVT_obj_request nviRequest)

You can make a request to know the object status.
Member Name
object_id
Stores the object ID.
H0
RQ_NORMAL
H1
RQ_DISABLED
H2
RQ_UPDATE_STATUS
H3
RQ_SELF_TEST
H4
RQ_UPDATE_ALARM
H5
RQ_REPORT_MASK
H6
RQ_OVERRIDE
H7
RQ_ENABLE
object_request
H8
RQ_RMV_OVERRIDE
H9
RQ_CLEAR_STATUS
HA
RQ_CLEAR_ALARM
HB
RQ_ALARM_NOTIFY_ENABLED
HC
RQ_ALARM_NOTIFY_DISABLED
HD
RQ_MANUAL_CTRL
HE
RQ_REMOTE_CTRL
HF
RQ_PROGRAM
HFF RQ_NUL
Other than the above
*1
Changes the invalid_request of the object status (nvoStatus) to "1" when data is set. (Refer to page 38)
*2
Use alarm reset (nviInvAlarmReset) to reset the alarm status of the inverter (Refer to page 49.)
*3
Can also be switched from switchover mode. (For details of switchover mode, refer to the inverter manual.)
Description
In external operation mode
, it shifts to the network
*3
operation mode.
Makes the inverter object invalid.
Update object status (nvoStatus).
Not supported.
*1
Updates in_alarm bit of the object status (nvoStatus).
Changes bit (invalid_id, invalid_request, disabled,
manual_control, in_alarm, in_override, report_mask)
supported by object status (nvoStatus) to "1".
Not supported.
*1
Makes the inverter object valid.
Not supported.
*1
Clears all bits of the object status (nvoStatus) to "0".
Clear in_alarm bit of object status (nvoStatus) to "0".
Not supported
*1
Shifts the inverter to the external operation mode.
Shifts the inverter to the network operation mode.
Not supported.
*1
Nothing is done.
Not supported.
*1
NETWORK VARIABLES
Initial
Value
H0
*2
6
37