Advertisement

NETWORK VARIABLES
6.8.8
Acceleration time (network input config SNVT_time_sec
nciRampUpTm)
You can set the time taken by the motor to accelerate from 0Hz to the set frequency (1 to 400Hz) of Pr. 20
Acceleration/deceleration reference frequency. (Refer to the inverter manual (applied) for details of Pr. 20.)
Data Name
nciRampUpTm
*1
The setting range changes according to the Pr. 21 Acceleration/deceleration time increments setting. At an initial
status of Pr. 21, the setting range is "0 to 3600.0s" and setting increments is "0.1s".
⋅ Data acceptance timing ........... At network variable receive (nv_update_occurs event)
REMARKS
Refer to the inverter manual (applied) for details of Pr. 7
CAUTION
The setting increments of acceleration time changes according to Pr. 21 settings. The value 0.1 times greater
than the setting value is written to the inverter when Pr. 21 = 1. When the Pr. 21 setting has been changed, set
the acceleration time again.
(Example) When Pr. 21 = "0" and the setting of acceleration time is "5.0"s, and if the setting of Pr. 21 is changed
to "1", the setting value of acceleration time will change to "0.5" s.
Refer to the inverter manual (applied) for details.
78
Initial Value
Initial value of Pr. 7
Range
Increments
*1
0.0s to 3600.0s
0.00s to 360.00s
Setting Value
Storage Location
0.1s/bit
Pr. 7
0.01s/bit