NETWORK VARIABLES
6.5.6
Output frequency monitor (0.1Hz increments) (network output
SNVT_freq_hz nvoInvOutFreq)
You can monitor the output frequency of the inverter in 0.1Hz increments.
Data Name
nvoInvOutFreq
⋅ Data send event ...................... When data changes in 0.1Hz increments
⋅ Data send timing ..................... As set in Pr. 388 Heartbeat send time interval and Pr. 389 Minimum heartbeat
REMARKS
This variable is similar to "output frequency monitor (0.005% increments)" but may sometimes differ from it in data
send timing since they are different in mutual resolution. (Refer to page 47)
46
Initial Value
0.0Hz
send time. (Refer to page 75)
Range
0.0Hz to 400.0Hz
Increments
0.1Hz/bit