Example of Inverter Parameter Clear

The
following
shows
LONWORKS communication again when inverter
parameter clear is performed from LONWORKS
communication.
(1) Perform parameter clear
Perform parameter clear via network or with the
operation panel or parameter unit.
When performing with the operation panel or
parameter unit, the procedure is the same as that of
the inverter.
When performing via the network (LONWORKS),
use
the
command
nviInvCmdReq) of network variables.
Data set by command request:
Request flag = H01
Request code = H00FC
Request data = H5A5A, H55AA
⋅ Parameter for communication is also cleared when
H9696 and H9966 are set as request data.
(Refer to page 65)
⋅ When Pr. 79 = "2", resetting is necessary as the set
value is cleared.
procedure
to
make
request
(SNVT_str_asc
(2) Check
the
status
variables
Set LonMaker Browser to "Monitor All On" to turn on
monitoring of the inverter network variables.
(When "Monitor All OFF" is set, only the initial value
of network variables the inverter sent to LonMaker
Browser can be referred. To always check network
variables, set "Monitor All On".)
(3) LONWORKS communication resetting is
complete
APPENDIX
of
the
network
93