en | Alarms and Relay Connections
3.
6.2.2

Configuring a Normally Closed Supervised Alarm

1.
2.
3.
F.01U.215.782 | 1.0 | 2011.04
From the AutoDome main menu, select Alarms Setup>Inputs Setup, and set the Alarm
Input # to N.O.S. See the table below for contact and condition details.
AutoDome Programmed N.O.S.
Contact
Alarm Condition
Open
Normal
Closed
Alarm
Cut or brake
Tamper
Install a 2.2 K end-of-line resistor in the alarm circuit.
Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to the ground (pin 7) at the
AutoDome.
2.2K
Figure 6.2 N.C.S. - Normally Closed Supervised Connections
1
Dry Contact
2
Alarm 1 or 2 only (Pin 5 or 6)
From the AutoDome main menu select Alarm Setup>Inputs Setup, and set Alarm Input #
to N.C.S. See the table below for contact and condition details.
AutoDome Programmed N.C.S.
Contact
Alarm Condition
Open
Alarm
Closed
Normal
Short
Tamper
Installation Manual
AutoDome 600 Series Analog PTZ Camera
3
Dome Connector
4
Ground (Pin 7)