PVI 3000S, 4000S, 5000S, 5300 Series Inverters
4.2
AC Wiring
WARNING: Reconfirm that the circuit breaker to the grid/utility is switched OFF
before connecting the power wires from the breaker to the inverter AC terminal
block.
Use #10 AWG to #6 AWG, 90 °C (194 °F) copper wire for all AC wiring connections to the PVI
3000S-5300 inverters. You must choose the appropriate wire size based on local code
requirements. Designed voltage drop recommended to being no greater than 1%. Larger
conductors will be needed for longer wire runs.
Installation and Operation Manual (Rev A)
Figure 4.1.6 –Utility Configurations
27