PVI 23TL & PVI 28TL Installation and Operation Manual 
 
WARNING: Solectria's side AC knockout can't be utilized 100%. It is blocked by a 
barrier  that  separates  High  Voltage  AC  cables  from  Communication  wires.  One 
loses about 25% of the area of the knockout due to this issue. 
 
 
4.2 
DC/AC Grounding  
PVI 23‐28TL inverters have a DC ground bar with four terminals that can be used to terminate the 
DC  equipment  ground,  each  terminal  can  accept  a  single  copper  conductor  ranging  from  6‐
10AWG (Torque = 14in‐lbs). As shown in Figure 4.3 below. 
 
 
PVI  23‐28TL  inverters  also  have  an  AC  ground  bar  with  four  terminals  that  can  be  used  to 
terminate  the  AC  ground.  Each  terminal  can  accept  a  single  copper  conductor  ranging  from  6‐
10AWG (Torque = 14 in‐lbs), a stud that fits a M5 nut to terminate the AC system ground (Torque 
=  14in‐lbs),  and  an  external  ground  point  (Torque  14in‐lbs).  The  stud  and  external  ground  can 
accept a single copper conductor ranging from 8‐10AWG.  
 
NOTE: The lug for the stud is located in the accessory box. 
DOCR‐070365‐E 
  
Figure 4.2 – AC Side Knockout Partially Blocked 
Figure 4.3 DC Equipment Ground 
 
 
PVI Series Inverters 
 
 
Page 22 of 57 