Terminal Function Selection - Toshiba TOSVERT VF-S9 Instruction Manual

Compact inverter 1-phase 200v class 0.2 2.2kw 3-phase 200v class 0.2 15kw 3-phase 400v class 0.75 15kw
Hide thumbs Also See for TOSVERT VF-S9:
Table of Contents

Advertisement

Parameter setting
Title
6.3

Terminal function selection

6.3.1
• Function
Parameter setting
6
Title
6.3.2
Use the above parameters to send signals from an external programmable controller to various control input
terminals to operate and/or set the inverter.
The desired contact input terminal functions can be selected from 51 types. This gives system design flexi-
bility.
Function
RST signal selection
Keeping an input terminal function always active (ON)
: Always-active function selection
This parameter specifies an input terminal function that is always to be kept active (ON). (Only one
function selectable)
Function
Always-active function selection
Modifying input terminal functions
: Input terminal selection 1 (F)
: Input terminal selection 2 (R)
: Input terminal selection 3 (RST)
: Input terminal selection 4 (S1)
: Input terminal selection 5 (S2)
: Input terminal selection 6 (S3)
Adjustment range
0: Standard setting
(reset on when RST-CC on to off)
1: Activated by turning RST off
(reset on when RST-CC off to on)
Adjustment range
0 ∼ 51 (See section 11)
F-6
E6580757
Default setting
0
Default setting
0