3.2.1
How to start and stop
(1) Start and stop using the operation panel keys (
Use the
and
RUN: Motor starts.
STOP: Motor stops (slowdown stop).
(2) Start and stop using external signals to the terminal board (
Use external signals to the inverter terminal board to start and stop the motor. (Set JP301 to sink logic)
Short F and CC terminals:
run forward
Open F and CC terminals:
slow down and stop
Frequency
F-CC
3.2.2
How to set the frequency
(1) Setting the frequency using the potentiometer on the inverter main unit
(
)
Set the frequency with the notches on the potentiometer.
keys on the operation panel to start and stop the motor.
* Coast stop
The standard default setting is for slowdown stop. To
make a coast stop, assign an ST terminal function to
an idle terminal using the programmable terminal
function. And set the
For coast stop, open the ST-CC when stopping the
motor in the state described at left. The monitor on
the inverter at this time will display
Motor speed
Slowdown stop
F-CC
ON
ST-CC
OFF
C-7
)
:ST signal selection.
Coast stop
Move clockwise through the higher
notches for the higher frequencies.
E6580757
)