If the motor is restarted in retry mode, this function will operate, regardless of the setting of this parameter.
1) Auto-restart after momentary power failure (Auto-restart function)
6
Setting
undervoltage by the main circuits and control power.
2) Restarting motor during coasting (Motor speed search function)
Setting
first and then connected again.
3) DC braking during restart
If this parameter is set to either "
will be conducted during the restart of the motor.
This function is effective when the motor is under a momentary power failure or coasting status and is re-
versing for some external reason.
Function
0: Disabled
1: At auto-restart after momentary stop
2: When turning ST-CC on or off
3: At auto-restart or when turning ST-CC on or off
Auto-restart control
4: Motion of DC braking at start-up (at auto-
selection
restart after momentary stop)
5: Motion of DC braking at start-up (when turning
ST-CC on or off)
6: Motion of DC braking at start-up (at auto-
restart or when turning ST-CC on or off)
Input voltage
Motor speed
F-CC
to , ( ): This function operates after power has been restored following detection of an
Motor speed
F-CC
ST-CC
to , ( ): This function operates after the ST-CC terminal connection has been opened
", "
", or "
F-24
Adjustment range
", DC braking specified by parameter
E6580757
Default setting
0
, or