Setting of electronic thermal protection characteristics selection
Setting value
Setting of motor electronic thermal protection level 1
5
Overload protection
×
×
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor
is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1
that it fits the motor's rated current.
Output current reduction factor
Note:
[Example of setting: When the VFS9-2007PM is running with a 0.4kW motor having 2A rated current ]
Key operated
LED display
Overload stall
×
×
: valid, × : invalid
[%]/[A]
Output frequency (Hz)
The motor overload protection start level is fixed at 30Hz.
Operation
Displays the operation frequency (perform during stop).
(When standard monitor display selection
[operation frequency])
Press the MON key to display the first basic parameter
(automatic acceleration/deceleration).
Press either the
key or the
.
Press the ENTER key to display the parameter setting. (Standard
default setting: 100%)
Press the
key to change the parameter to
(= motor rated current/inverter output rated current x 100 =
2.0/4.8 x 100).
(When PWM carrier frequency
Press the ENTER key to save the changed parameter.
and the parameter set value are displayed alternately.
E-20
E6580757
is set to
key to change the parameter to
is set to 12kHz.)