1) If the detection band value + the set frequency is less than the designated fre-
quency
6.2

Input signal selection

6.2.1
6
• Function
Parameter setting
Title
Set frequency speed reach detection signal
RY-RC
P24-OUT
FLA/FLC/FLB
Set frequency speed reach signal: Inverted
Changing the standby signal function
: ST (standby) signal selection
The F103 parameter specifies standby function activation timing, depending on the particular status of
the ST (standby) signal.
1) Standby on only when ST is on (ST-CC on: Standby, ST-CC off: Gate off [Coast stop])
2) Standby always on
3) Synchronized with F/R (F/R-CC on: Forward/reverse run, F/R-CC off: Coast stop)
4) Standby on only when ST is off (ST-CC off: Standby, ST-CC on: Gate off [Coast stop])
Function
ST signal selection
Output frequency [Hz]
Adjustment range
0: Standby on when ST is on
1: Standby always on
2: Interlocked with F/R
3: Standby on when ST is off
F-4
E6580757
Time [sec]
Default setting
1