9
Parallel operation
9.1
Functionality
PROTECT C. 6000 (S) and C. 10000 (S) was developed for
the parallel operation in n+x technology ("n" stands for the
number of necessary appliances for load supply, "x" stands
for the redundancy level). Up to three appliances of the same
type can be connected in parallel to raise the output power
and/or to receive a higher availability.
The following constellations are possible according to the n+x
technology:
1 + 0 Use of 1 unit
1 + 1 Use of 2 units
1 + 2 Use of 3 units
2 + 0 Use of 2 units
2 + 1 Use of 3 units
3 + 0 Use of 3 units
max. 6 or 10 kVA
max. 6 or 10 kVA
max. 6 or 10 kVA
max. 12 or 20 kVA
max. 12 or 20 kVA
max. 18 or 30 kVA
49
No redundancy
Single redundancy
Double redundancy
(max. configuration level)
No redundancy
Single redundancy
(max. configuration level)
No redundancy
(max. configuration level)