4.20 Position Sensor Abnormality
H6
Error Code
Method of Error
A compressor start-up failure is detected by checking the compressor running condition through the
Detection
position detection circuit.
Error Decision
If the error repeats, the system is shut down.
Conditions
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Power supply voltage out of specification
Causes
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage out of specified range
Service Diagnosis
Troubleshooting