Falcon SSG1.5KRM-1 Owner's Operating Manual page 40

Ssg series rackmount industrial-grade ups plus
Hide thumbs Also See for SSG1.5KRM-1:
Table of Contents

Advertisement

SSG-HW Series
Model Number
Nominal VA
Electrical Input
Nominal AC Voltage
AC Voltage Range
Frequency
Power Factor Correction
Surge Suppression
Efficiency (Typical)
Electrical Output
Watts
AC Voltage
(User Programmable)
Frequency
Frequency Stability
Voltage Regulation
Step Load Change
Harmonic Distortion
Overload
Crest Ratio
Battery
DC Bus Voltage
Back Up Time
@Full Load
@1/2 Load
Battery Pack Type
Number of Battery Packs (48Vdc)
Recharge Time
Transfer Time
Line Fails/Recovers
UPS to Bypass or Reverse
After Overload
With Frequency Converter Options
Electrical Connections
Input
Output
Environmental
Temperature
Operational
Storage
Humidity
Altitude
Cooling
Heat Dissipation
(BTU/Hour)
Audible Noise
@ 1 Meter
Controls & Indicators
LCD Display
Audible Alarms
Load Segment Control
Remote Emergency Power Off (or)
Remote Output Receptacle Control
Communications
Mechanical
Dimensions UPS
inches (mm)
H x W x D
Standard Battery Module
Weight
lb. (kg)
Battery Bank
Agency Listing
©
2011 Falcon
®
Electric, Inc. All rights reserved. Falcon
All other brand names and trademarks are the property of their respective owners.
Falcon Electric, Inc. - 5116 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720
TM
Industrial-Grade UPS PLUS
SSG2.2RM-1-HW
SSG2.2RM-2-HW
2200
1540
50/60 Hz (Auto Tracking or user programmable fixed 50 or 60Hz modes)
± 0.3% (Battery Mode), ±5% Synchronized to the input frequency in utility mode
8 minutes
20 minutes
Battery packs are replaceable through the front panel without removing the UPS, battery bank or EBM from the rack
Long-life, 8 to 10 Year, Maintenance-Free, Sealed VRLA Batteries, 12Vdc, 7AH
-1 Models = 6' line cord with 5-20P
-2 Models = 6' line cord with Schuko
The plug may be removed and cord used to hardwire
784
MIMIC Graphical Display, Input/Output Voltage, Frequency & Load, Alarm, Programmable settings & UPS state icons
DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm
(Standard)
Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)
(Optional) UPS Load Segment Controlled Output Receptacles can be turned off and on using a remote isolated switch contact.
USB Port, RS-232C Serial Port, Optional SNMP/HTTP Agent Board
UPS
-1 Models UL 1778, CUL, FCC Class B, -2 Models CE,UL 1778, CUL
®
and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.
www.falconups.com - email: sales@falconups.com
-1 Models =120Vac
-2 Models = 208-240Vac
-1 Models = 80-138Vac
-2 Models = 160-276Vac
50/60 Hz ± 5% (Auto Tracking)
> 0.97
IEEE/ANSI C62.41
> 87%
-1 Models = 100, 110, 115 or 120Vac (sinewave)
-2 Models = 208, 220, 230, 240Vac (Sinewave)
Voltage Regulation
± 7% for 100% load variation, recovery in 5ms
< 3% Linear Load, < 5% Non-Linear Load
150% for 10 seconds, 110% for 20 seconds, 105% for 50 seconds
3:1
96Vdc
User-Replaceable, Hot-Swappable individual 48Vdc packs
(2)
8 Hours to 90%
Zero
< 4ms
Auto Transfer to UPS
Bypass Disabled
Hardwire Terminal Block
-20ºC to +40º C (-4ºF to 104ºF)
-15ºC to +50ºC (5ºF to 122ºF)
10% to 95% Non – Condensing
10,000 Feet (3000 meters) without derating
Low Velocity Forced Air Fans
<50dBA
Two programmable load segments, one continuous load segment
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
(2U) 3.5 x 16.8 x 21.3 (88.5 x 426 x 540)
32 (14.5)
70.6 (32.1)
40
®
2.2kVA - 3kVA
SSG3KRM-1-HW
SSG3KRM-2-HW
3000
2100
6 minutes
18 minutes
-1 Models = 6' line cord with L5-30P
-2 Models = 6' line cord with Schuko
The plug may be removed and cord used to hardwire
1071
(UPS Bundled UPSilon Software)