Battery Module Installation:
1. Mount the battery module directly above or below the UPS or battery module in the
equipment rack.
2. Verify the battery disconnect is in the off postion.
3. Remove the battery inteconnect connector cover plate located on the module rear
panel.
4. Connect the battery cable to the newly installed battery module. Next, connect the
other end of the cable to the UPS.
5. If the an extended module is being installed, verify all battery module battery
disconnect switches are turned to the "off" position. Two battery interconnect
connectors are provided on each battery module to allow for a daisy chain
connection to all modules and the UPS.
Performing a Manual Battery Test:
Pressing the "Function/Test" button for three seconds while the UPS is operating in Normal Mode will
initiate a manual battery test. If the UPS goes to Battery Mode and returns to Normal On-line Mode
after 10 seconds, the batteries are good.
If a single, long audible tone is sounded and the unit does not switch to battery mode, this indicates
that either the batteries are defective, installed incorrectly, the battery pack is not installed, the
battery bank interconnect cable is not installed, or the battery doscpnnect(s) are not in the "on"
position. If the problem cannot be resolved, contact Falcon Service.