Falcon SG800-1T Owner's Operating Manual

Falcon SG800-1T Owner's Operating Manual

Sg series ups plus

Advertisement

SG2K-1T, SG2K-2T, SG2K-1TX & SG2K-2TX & SG2K-1TXI & SG2K-2TXI
SG3K-1T, SG3K-2T, SG3K-1TX & SG3K-2TX & SG3K-1TXI & SG3K-2TXI
Detailed SG Series product specifications are available in PDF format at
FALCON
®
Electric Inc., 5116 Azusa Canyon Rd., Irwindale, California 91706, (626) 962-7770, Fax 626-962-7720, Email: sales@falconups.com
2011 Falcon
®
Electric Inc. All rights reserved.
All other brand names and trademarks are the property of their respective owners.
The information stated in this document is subject to change without notice. 2011-09-15
®
®
Falcon
, Falcon
Electric and UPS Plus
OM48021-1-3K Rev. H
OWNER'S
OPERATING
SG Series
Uninterruptible Power Supply Models:
SG800-1T, SG800-2T
SG1K-1T, SG1K-2T, SG1.5K-1T & SG1.5K-2T
-1T & -2T Models
®
logos are registered trademarks of Falcon Electric, Inc.
MANUAL
TM
UPS Plus
®
-1TX & -2TX & -1TXI & -2TXI
www.falconups.com

Advertisement

Table of Contents
loading

Summary of Contents for Falcon SG800-1T

  • Page 1 All other brand names and trademarks are the property of their respective owners. The information stated in this document is subject to change without notice. 2011-09-15 ® ® ® Falcon , Falcon Electric and UPS Plus logos are registered trademarks of Falcon Electric, Inc. OM48021-1-3K Rev. H...
  • Page 2: Table Of Contents

    Battery Replacement . Storing the UPS and Batteries. FCC Considerations Technical Support & RMA Procedure . Requesting Technical Information or Support. FALCON Web Support . Warranty Specifications . SG800VA - SG1.5KVA . SG2KVA - SG3KVA -1TX, -1TXI. SG2KVA - SG3KVA all other models. .
  • Page 3: Sg Ups Features

    SG SERIES UPS FEATURES True Double Conversion On-Line Design Input Power Factor Correction Wide Input Voltage Window Pure Sinewave Output Precision Output Voltage Regulation Superior Brownout, Surge and Transient Protection Internal System Bypass Eliminates Generator Frequency & Voltage Drift Microprocessor Control & RS-232 Communications UPSILON ®...
  • Page 4: Important Safety Instructions (Read First)

    CAUTION This UPS utilizes voltage that may be hazardous. Do not attempt to disassemble. This unit contains no user replaceable parts. Refer all servicing to Falcon Electric, Inc. CAUTION THIS UPS IS NOT INTENDED TO BE USED IN CONJUNCTION WITH LIFE SUPPORT OR OPERATING ROOM EQUIPMENT.
  • Page 5: Sg Series Ups Overview

    Whether your application requires a few additional minutes or hours, the SG Series will be ready. Falcon also offers optional battery charger upgrades for faster recharging. Please specify your extended battery and charger requirements at the time of your initial order.
  • Page 6: Installation Instructions

    CHAPTER 2 CHAPTER 2 INSTALLATION INSTRUCTIONS Verify the following is included in the UPS shipping carton: (1) UPS, (1) Software Diskette(s) & Manual, (1) Power Cord (800VA-1KVA models only), (1) Owners Manual & (1) UPS/Computer Cable. Verify the UPS unit is configured for the proper input/output voltage and frequency. This information is stated on the nameplate label located on the rear or the side panel of the unit.
  • Page 7 UPS/Computer cable to the DB-9 connector located on the UPS rear panel. Then install the shutdown and monitoring software provided with the UPS. For your reference, UNIX shutdown and monitoring software is available from Falcon Electric at an additional cost.
  • Page 8: Dip Switch Settings Diagrams

    VIEW OF DIP SWITCHES LOCATED ON THE UPS REAR PANEL SWITCH SETTINGS FOR -1 MODELS SWITCH SETTINGS FOR -2 MODELS GREEN MODE SWITCH SETTINGS FOR ALL MODELS...
  • Page 9: Extended Battery Bank Interconnection

    TYPICAL EXTENDED BATTERY BANK & UPS INTERCONNECTION (Mini-tower models shown; same applies for floor standing banks) TYPICAL 1ST CABLE BATTERY CONNECTOR TO ADD MORE BANKS, DAISY CHAIN TO NEXT BANK FROM THIS 2ND CABLE BATTERY FUSE OPTIONAL BATTERY OPTIONAL BATTERY CHARGER CIRCUIT CHARGER CIRCUIT BREAKER...
  • Page 10: Extended Battery Bank Installation Procedure

    SG800VA-3kVA TOWER EXTENDED BATTERY BANK SELECTION GUIDE FOR 800VA-1KVA MODELS FOR 1.5KVA-2KVA MODELS FOR 3KVA MODELS NOTE: The backup times stated are for reference only. Backup time may vary due to the type of load, battery age or condition, environmental conditions, etc.
  • Page 11: Operation

    CHAPTER 3 CHAPTER 3 OPERATION UPS FRONT PANEL INDICATOR AND FUNCTION KEYS LOAD LEVEL INDICATOR LEDS *The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS. *The second LED is lit when the output load is greater than 50% of the rated output of the UPS.
  • Page 12 BYPASS INDICATOR LED When this LED is lit the UPS bypass is active. Should the Alarm LED be lit at the same time, the UPS detected an internal failure and the UPS must be serviced. INVERTER INDICATOR LED When this LED is lit, the UPS inverter is operating and powering the connected load. GREEN MODE LED INDICATOR This LED is lit when the connected output load of the UPS drops to under 10% of the full rated output of the UPS, providing SW3 is in the "down"...
  • Page 13: Audible Alarms

    AUDIBLE ALARMS Audible alarm signals are divided into two different levels of alarm status. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. Category one alarms: a. Two short beeps followed by three short beeps. Notifies the user that the SG UPS is configured with the optional battery pack and is in BATTERY MODE.
  • Page 14: Rear Panel Details

    CHAPTER 4 CHAPTER 4 REAR PANEL DETAILS SG800-1T & SG1K-1T Typical Rear Panel Overview COVER PLATE FOR OPTIONAL  COMMUNICATIONS INTERFACE BAORD SG800-2T & SG1K-2T Typical Rear Panel Overview COVER PLATE FOR OPTIONAL  COMMUNICATIONS INTERFACE BAORD Please verify the UPS output rat- ings match your requirement...
  • Page 15: Sg1.5K-1T, Sg2K-1T & Sg3K-1T Rear Panel

    SG1.5K-1T, SG2K-1T & SG3K-1T Typical Rear Panel Overview BATTERY FUSE OUTPUT RECEPTACLES (6) NEMA 5-15R STANDARD SG1.5K-2T, SG2K-2T & SG3K-2T Typical Rear Panel Overview COOLING FANS DO NOT BLOCK BATTERY FUSE OUTPUT RECEPTACLES Shown with (1) L6-20R & (2) 6-20T Receptacles...
  • Page 16: Sg2K-Xtx & Txi & Sg3K-Xtx & Txi Rear Panel

    SG2K-1TX, SG2K-2TX, SG2K-1TXI, SG2K-2TXI, SG3K-1TX, SG3K-2TX, SG3K-1TXI & SG3K-2TXI Typical Rear Panel Overview 208-240Vac RECEPTACLE OUTPUT FUSES (2) PLACES MAIN POWER SWITCH & INPUT CIRCUIT BREAKER BREAKER 120Vac OUTPUT RECEPTACLES SG2K-1TXI, SG2K-2TXI & SG3K-1TXI, SG3K-2TXI Output Configuration The SG -2TXI models provide three galvanically isolated 240Vac and 120Vac outputs. The two 120Vac receptacles are an isolated and are derived split phase from the isolated, center tapped 240Vac output.
  • Page 17: Communications Interfaces

    Internal SNMP/HTTP agent option installed into the UPS communications option slot. The following options WILL NOT affect the operation of the RS-232 port: Falcon Opto Coupler based signal interface board installed to the communications option slot. Any Falcon relay based, dry contact signal interface board installed into the communications option slot.
  • Page 18: Contact Closure & Opto Interface Options

    DRY CONTACT & OPTO COUPLER  INTERFACE BOARD OPTIONS Typical Falcon Dry Contact Relay Board PIN & JUMPER ASSIGNMENT FOR THE FALCON  UA88374 RELAY OPTION BOARD (no on-bypass signal) PIN & JUMPER ASSIGNMENT FOR THE FALCON  UA88376 RELAY OPTION BOARD (with on-bypass signal)
  • Page 19 Typical Falcon Opto-coupler Interface Card PIN ASSIGNMENT FOR THE FALCON  UA88373 OPTO-COUPLER OPTION BOARD (no-bypass signal) OPTO Board Internal Circuitry...
  • Page 20 APC Style Dry Contact Relay Board PIN & JUMPER ASSIGNMENT FOR THE FALCON  UA88377 RELAY OPTION BOARD (APC Style Board)
  • Page 21: Maintenance & Technical Support

    In home, office or computer room environments, the batteries should be replaced every three to five years. Should you require battery replacement, contact the Falcon Service Department (see page 21 for contact information). WARNING Never attempt to service batteries.
  • Page 22: Storing The Ups And Batteries

    The following precautions should be observed by a qualified technician when working with batteries: Remove watches, rings, or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of batteries. Storing the UPS and Batteries Should you need to store the UPS for a long period, fully recharge the battery just prior to storage and recharge the battery every 4 months by plugging the...
  • Page 23: Technical Support & Rma Procedure

    You may request technical information or support by email or telephone. Please send your technical or support questions by email to: SUPPORT@FALCONUPS.COM You may contact a FALCON support engineer directly by calling the FALCON support line between 9:00 am and 4:00 pm PST. 800.842.6940 FALCON Web Support...
  • Page 24: Warranty

    Falcon with an RMA number. For defective product returned within 30 days of shipment, Falcon will pay for shipping costs to and from its service center. For defective product returned after 30 days but within 90 days of shipment, Falcon will only pay for shipping costs in sending the new or repaired product back to the end-user.
  • Page 25: Specifications

    800VA to 1.5kVA SG Series UPS PLUS ®...
  • Page 26: Sg2Kva - Sg3Kva -1Tx, -1Txi

    2kVA - 3kVA SG Series UPS PLUS ® -1TX & -1TXI...
  • Page 27: Sg2Kva - Sg3Kva All Other Models

    2kVA & 3kVA SG Series UPS PLUS ®...