Setting The Ups Output Voltage - Falcon SSG1.5KRM-1 Owner's Operating Manual

Ssg series rackmount industrial-grade ups plus
Hide thumbs Also See for SSG1.5KRM-1:
Table of Contents

Advertisement

How to Enable or Disable Green Mode (Function Bit 2)
To Enable:
1. Press the "Function/Test" and "Set/Alarm Silence" buttons at same time and
hold them for one second. The unit will sound one beep and then enter the
Configuration Mode.
2. Press the "Function/Test" button two times to move the dot from function BIT 0
to function BIT 2 (The Green Mode function).
3. Press the "Set/Alarm Silence" button to enable (NO DOT) BIT 7. (The reverse of
other feature enable settings)
4. Press the "Set/Alarm Silence" and "Function/Test" buttons at same time again
and hold for one second. The alarm will sound one short beep to acknowledge
the UPS has stored the setting.
To Disable: (Factory Default)
1. Press the "Function/Test" and "Set/Alarm Silence" buttons at same time and
hold them for one second. The unit will sound one beep and then enter the
Configuration Mode.
2. Press the "Function/Test" button two times to move the dot from function BIT 0
to function BIT 2 (Green Mode function).
3. Press the "Set/Alarm Silence" button to turn off (DOT) BIT 7. (The reverse of other
feature disable settings)
4. Press the "Set/Alarm Silence" and "Function/Test" buttons at same time again
and hold for one second. The alarm buzzer will sound one short beep to acknowledge
the UPS has stored the setting.
How to Set the UPS Output Voltage (Function Bits 0 & 1)
The SSG Series UPS is shipped configured from the factory with its output voltage set to 120Vac.
For most North American applications, the UPS output voltage will not have to be changed.
CAUTION: NEVER CHANGE THE UPS OUTPUT VOLTAGE WHILE IT HAS EQUIPMENT
CONNECTED TO ITS OUTPUT RECEPTACLES.
Make output voltage configuration changes and verify the desired output voltage is present at the
UPS output using the UPS output voltage display function. Next, verify that all of the equipment to be
connected to the UPS will operate satisfactorily on the newly selected output voltage.
CAUTION:
When the UPS output voltage is set to 100Vac, the maximum amount of load that
can be connected to the UPS must be derated (reduced) by 15%.
Output
Function BIT(s)
Voltage
120Vac
BIT 0 & BIT 1
115Vac
BIT 0 & BIT 1
110Vac
BIT 0 & BIT 1
100Vac
BIT 0 & BIT 1
Green Mode Setup
Status Bit (BIT 7)
For BIT 0, set bit 7 On (Dot), For BIT 1, set bit 7 On (Dot) (default)
Fro BIT 0, set bit 7 Off (No Dot), For BIT 1, set bit 7 On (Dot)
For BIT 0, set bit 7 On (Dot), For BIT 1, set bit 7 Off (No Dot)
For BIT 0, set bit 7 Off (No Dot), For BIT 1, set bit 7 Off (No Dot)
21