Combustion-Air And Vent Pipe Connections - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

Series 180 4-vvay mumtipoise dkect-vent variabme-capacity condensing gas furnace
Table of Contents

Advertisement

--9
In Canada,
construct
all combustion-air
and vent pipes %r this unit
of CSA
or UL(
listed
schedule-40
PVC,
PV(-DWV
or ABS-
DWV
pipe
and
pipe
cement.
SDR
pipe
is NOT
approved
in
Canada
NOTE:
Furnace
corubustion-air
and vent
pipe
connections
are
sized for 2-in. pipe. Any pipe size change
should be made outside
fmnace
casing
in vertical
pipe. (See Fig. 33.) This allows
proper
drainage
of vent condensate.
Combustion-air
and vent pipes
must
tem_inate
together
in same
atmospheric
pressure
zone,
either
through
roof or sidewall
(roof
tem_ination
preferred),
using
accessory
termination
kit.
See Table 6 for required
clearances.
Furnace
combustion-air
and vent pipe
connections
must
be at-
tached
as shown
in Fig. 34. Combustion-air
intake plug fitting and
inducer
housing
alternate
vent
cap may
need to be relocated
in
some applications.
NOTE:
Slope combustion-air
and vent pipes a mininmm
of 1/4
in. per linear
ft with no sags between
hangers.
MINOR
PROPERTY
DAMAGE
Failure
to %llow
this
caution
may result
in water
damage
from condensate
dripping.
When
combustion-air
pipe
is installed
above
a suspended
ceiling,
pipe must
be insulated
with
3/8-in.
thick Armaflex-
type insulation
Combustion°air
pipe should also be insulated
when
it passes
through
a warn% humid
space.
[NIT
MAY
NOT
OPERATE
Failure
to follow
this caution
may result
in intem_ittent
unit
operation.
When vent pipe is exposed
to temperatures
below
fi'eezing,
such as when it passes
through
an unheated
space
or when a
chimney
is used
as a raceway,
pipe
must
be insulated
as
shown
in Table
8 with Armaflex-type
insulation
NOTS:
Select 1 vent pipe connection
and
1 combustion-air
pipe connection
AIR
COMBUSTION-AIR
7
COMBUSTION-AIR
UPFLOW
COMBUSTION-
AIR
VSNT
HORIZONTAL-LEFT
DISCHARGE
NOTE:
Select 1 vent pipe connection
and
1 combustion-aB
pipe connection
COMBUSTION-
_
COMBUSTION-
AIR
AiR
AIR
FLOW
DOWNFLOW
COMBUSTION-
AiR
VENT
HORIZONTAL-RIGHT
DISCHARGE
A96187
Fig. 34-=Combustion-Air
and Vent Pipe
Connections
UNIT
CORROSION
HAZARD
Excessive
exposure
to contaminated
combustion
air
may
result
in safety
and perfbt_nance
related
problems.
Combustion
air
must
not
be taken
flora
inside
structure
because
that
air
is fiequently
contaminated
by halogens,
which
include
fluorides,
chlorides,
bromides,
and iodides.
These
elements
are fbund
in aerosols,
detergents,
bleaches,
cleaning
solvents,
salts, air f?esheners,
adhesives,
paint,
and
other household
products
Locate
combustion-air
inlet as far
as possible
from swimming
pool
and swimming
pool pump
house,
(
NOT IN
HORIZONTAL
SECTION
FURNACE
TRANSITION
IN
VERTICAL
SECTION
A93034
Fig. 33--Combustion-Air
and Vent Pipe Diameter
Transition
Location and Elbow Configuration
FIRE
AND
EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in fire, property
damage,
personal
ir_jury_ or death.
Solvent
cements
are
combustible.
Keep
away
ti'om
heat,
sparks,
and open
flame.
Use only
in well ventilated
areas.
Avoid
breathing
in vapor
or allowing
contact
with
skin or
eyes.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this
warning
could
result
in
property
damage,
pe*sonal
il_iu*y, or death.
All
combustionoair
and
vent
pipes
must
be
airtight
and
watertight.
Pipes must also tem_inate
exactly
as shown in Fig.
37, 38, 39, 40, or 41.
NOTE:
The minimum combustion=air and vent pipe lengd_ (each)
for these fhmaces is 5 ft, Short pipe lengths (5=8 ft) may discharge
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents