Accessories; Removal Of Existing Furnaces From Common Vent Systems; Combustion-Air And Vent Piping; Direct Venting - Carrier 58MVP Installation, Start-Up, And Operating Instructions Manual

Series 180 4-vvay mumtipoise dkect-vent variabme-capacity condensing gas furnace
Table of Contents

Advertisement

-->
NOTE:
For additional thermostat connection diagrams, reference
Fig 54o61
AC( ESSORIES
1. Electronic
Air Cleaner
(EAC)
The furnace
control
EAC terminals
are energized
with
115v
(1.0=amp
maximum)
during
blower
operation.
Connect
an accessory
Electronic
Air Cleaner
(if used) using
1/4-in.
female
quick connect
terminals
to the two male
1/4=in.
quick-connect
terminals
on the control
board
marked
EAC-1
and EAC=2.
The terminals
are rated fbr 115VAC,
1.0 amps
maximum
and are energized
during
blower
motor
operation.
(See Fig. 32.)
2. Humidifier
(HUM)
Connect
an accessol T 24 VAC,
0.5 amp maximum
humidifier
(if used) to the 1/4-in. male quickoconnect
HUM
terminal
and
Co,,>24V
screw tem_inal
on the control board thet_nostat
strip.
The HUM
terminal
is energized
when blower
is energized
in
heating.
(See Fig. 32.)
[NIT
DAMAGE
HAZARD
Failure
to follow
this caution
may result
in unit component
damage.
DO NOT
connect
fhrnace
control
HUM
terminal
to HUM
(humidifier)
terminal
on Tlaermidistat
TM,
Zone
(ontIoller
or
similar
device.
See Them_idistag
xi, Zone Controller,
ffiermo°
stat,
or controller
manui:acmrer's
instructions
for proper
connection.
Step
9--Direct
Venting
The 58MVP
furnaces
require
a dedicated
(one
58MVP
furnace
only)
direct=vent
system.
In a direct-vent
system,
all air
for
combustion
is taken directly
fi'om outdoor
atmosphere,
arid all flue
gases are discharged
to outdoor
atmosphere.
REMOVAL OF EXISTING FURNACES FR()M
(OMMON
VENT SYSTEMS
When an existing
Category
I furnace
is removed
or replaced,
the
original
venting
system
may no longer
be sized
to properly
vent
the remaining
attached
appliances.
An improperly
sized CategoQ"
I venting
system
could
cause
the formation
of condensate
in d_e
furnace
and vent, leakage
of condensate
and combustion
products,
and spillage
of comhustion
products
into the living
space,
etc.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to fbllow
the steps outlined
below
for each appliance
connected
to the venting
system
being
placed
into operation
could
result
in carbon
monoxide
poisoning
or death.
The
fPllowing
steps
shall
be followed
fbr each
appliance
connected
to the venting
system
being placed
into operation,
while all other appliances
connected
to the venting
system
are
not in
operation:
1. Seal any unused
openings
in venting
system.
2. Inspect
d_e venting
system
for proper
size and horizontal
pitch, as required
in the National
Fuel Gas (;ode, ANSI
Z223AiNFPA
54 or dae CSA
B149.1.
Natural
Gas and
Propane
Installation
Code and these
instructions.
Deter-
mine that
there
is no blockage
or restriction,
leakage,
corrosion
and other
deficiencies,
which
could
cause
an
urisafc condition.
3. As fhr as practical,
close all building
doors and windows
and all doors
between
the
space
in which
the
appli=
ance(s)
connected
to the venting
system
are located
and
other spaces
of the building.
4. Close fireplace
dampers.
5. Turn on clothes
dcgers
and any appliance
not connected
to the venting
system.
Turn on any exhaust
fans, such as
range hoods
and bathroom
exhausts,
so they are opera°
ing
at maximum
speed.
Do
not
operate
a summer
exhaust
fhn.
6. Follow
the
lighting
instructions.
Place
the
appliance
being
inspected
into operation.
Adjust
the thermostat
so
appliance
is operating
continuously.
7. Test for spillage
fiom draft hood equipped
appliances
at
the &aft hood
relief
opening
after
5 minutes
of main
burner
operation.
Use d_e flame
of a match
or candle.
8. If improper
venting
is observed
during
any of the above
tests, the venting
system
must be corrected
in accordance
with the National
Fuel Gas (7ode, ANSI
Z223AiNFPA
54 and/or
CSA B 149.1, Natural
Gas and Propane
Instal°
tation Code,
9 After
it has been
dete*mined
that each
appliance
con=
nected
to the venting
system
properly
vents when
tested
as outlined
above,
return doors,
windows,
exhaust
rims,
t_replace dampers
and any other gas°fired
burning
appli°
ante to their previous
conditions
of use
Vent
system
or vent connectors
may need to be resized.
For any
other
appliances
when
resizing
vent systems
or vent connectors,
system
or connector
must
be sized
to approach
minimum
size as
determined
using appropriate
vent sizing table
%und in the NFGC
or NSCNGPIC
COMBUSTION=AIR
AND VENT
PIPING
General
Combustion_air
and vent pipe, fittings,
primers,
arid solvents
must
con%tin
to American
National
Standards
Institute
(ANSI)
stan-
dards
arid American
Society
%r Testing
and Materials
(ASTM)
standards.
See Table 5 for approved
materials
for use in the U.S.A.
See Table 7 fbr maximum
pipe lengths
and Fig. 37, 38, 39, 40, and
41 fk_r exterior
piping
an'angements.
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents