11.3 Reading and programming the configuration parameters

The configuration parameters are used to set the operating mode of the controller, that is to assign the humidifier's essential
functions.
The configuration parameters are divided into three groups:
Parameters for configuring standard operation (operating mode and types of probes), identified by codes from A0 to A9:
see Table 11.3.1.
Parameters for configuring the operation of accessory devices, identified by codes from b0 to b7: see Table 11.3.2.
Parameters for the setting the serial connections and remote control, identified by codes from C0 to C7: see Table
11.3.3.
These parameters can be accessed only by password to prevent the unwanted modification of the configuration.
code
range of
default
disp.
variation
0,.., 3
A0
0, 1
A1
0, .., 4
A2
A3
0, .., (A4)
A4
(A3), .., 255 *
100
A5
-10.0, ..., 10.0
0, .., 4
A6
0, .., (A8)
A7
A8
(A7), .., 100
100
-10.0, ..., 10.0
A9
*: see WARNING to side of Fig. 11.1.
code
range of
default
disp.
variation
b0
0, .., 199
**
b1
0, .., 3
2, .., 19.9
3.0
b2
70, .., 90
80
b3
b4
0, .., 2000
b5
0, .., 2000
2000
0, .., 2000
2000
b6
b7
0, .., 100
50
**: the default value depends on the size of the humidifier.
Carel code +030221761
parameters for configuring standard operation
unit of
description
measure
3
operating mode
0
unit of measure
1
signal applied to ambient probe input
can only be accessed in slave or
autonomous regulation (A0=1, 2 or 3)
0
% rH
ambient probe minimum
% rH
ambient probe maximum
0
% rH
ambient probe calibration
1
signal applied to the supply probe input
can only be accessed in autonomous
regulation with supply probe (A0=3)
0
% rH
supply probe minimum
% rH
supply probe maximum
0
% rH
supply probe calibration
parameters for configuring the operation of accessory devices
unit of
description
measure
s
period of modulation (if set to 0 modulation is disabled)
0
special functions
can not be accessed in ON/OFF mode
(A0=0)
%
pre-heating start offset
% rH
(referred to the pre-heating
°C
temperature Set Point)
0
supply water conductivity: if set to 0 the conductivity is measured automatically, otherwise,
S/cm
the set value is used
conductivity pre-alarm threshold
S/cm
conductivity alarm threshold
S/cm
%
regulation of the foam detection threshold (if set to 0 foam detection is disabled)
0=ON/OFF command
1= slave regulation
2=autonomous reg. with ambient probe
3=autonomous reg. with ambient probe and
supply probe
0=°C, kg/h
1=°F, lb/h
0=0/1V
1=0/10V
2=2/10V
3=0/20mA
4=4/20mA
can only be accessed in autonomous regulation
(A0=2 or 3)
0=0/1V
1=0/10V
2=2/10V
3=0/20mA
4=4/20mA
can only be accessed in autonomous
regulation with supply probe
(A0=3)
0 = no function
1 = pre-heating
2 = dehumidification
3 = pre-heating and dehumidification
can only be accessed with pre-heating
function enabled (b1=1 or 3)
35
preliminary version - rel. 2.0 - 03/09/99
heaterSteam
Tab. 11.3.1