11. READING AND PROGRAMMING THE PARAMETERS OF THE TYPE H
OR T CONTROL MODULE
The numerical, configuration and control panel parameters are grouped into three levels:
1. LEVEL 1 - Set Point, that is the value of the appliance's main setting St, accessible directly via the keypad for both
reading and modification.
2. LEVEL 2 - regulation parameters and measurements, that is the physical vales measured and the functional parameters
involving the regulation of the humidification process; these too can be accessed directly via the keypad for reading and
modification.
3. LEVEL 3 - configuration parameters consisting of the data needed to customise the control, according to the
requirements of the humidifier. These parameters are can be accessed only by password, to prevent the unwanted
modification of the configuration and thus the humidifier's essential functions.
Each parameter is composed as follows:
code
range of variation
default
unit of measure
Fig. 11.1

11.1 Reading and programming the Set Point

To read and/or change the Set Point, proceed as follows:
press the SEL button for around 2 seconds, until St appears;
on releasing the button, the unit of measure of the Set Point is displayed for 1
second, and finally the current set value;
to change the Set Point, press the
is being performed on the display;
press the SEL or PRG button to confirm the value displayed and conclude the
programming of the Set Point.
The characteristics and the range of variation of the Set Point are listed in Table 11.1.1.
type H control module
type T control module (for steam baths)
11.2 Reading
and programming
measurements
The regulation parameters represent the values relating to the process of ambient humidity (or temperature) control and are
identified by a code ranging between P0 and P9, according to the criteria described in Table 11.2.1.
The readings are on the other hand the physical values measured by the transducers connected to the control, depending on the
model and the setting of the humidifier, and the number of operating hours from the previous reset; the measurements are
identified by a code ranging between d1 and d9 (see Tab. 11.2.2).
Carel code +030221761
alphanumeric symbol appearing on the display corresponding to the parameter in
question
limit values within which the parameter can be modified
value set in the factory for the parameter
symbol displayed showing the unit of measure used for the parameter
Warning: the numerical values from 200 a 255 are displayed with the symbol
in the place of the hundreds digit 2 (due to the specific constructive configuration
of the display).
Figure 11.1 shows how the number 215 is displayed.
and
buttons, checking that the action
unit of
default value
measurement
% rH
50
°C
30
the
regulation parameters - reading the
33
Tab. 11.1
Press for 2
seconds
minimum limit maximum limit
0
0
preliminary version - rel. 2.0 - 03/09/99
heaterSteam
Fig. 11.1.1
P7
50
Tab. 11.1.1