Dipswitches - Gree E-TAC Installation And Operation Instructions Manual

Packaged terminal air conditioner/heat pump 7000-15000 btuh
Hide thumbs Also See for E-TAC:
Table of Contents

Advertisement

DIP
SWITCHES
Auxiliary
dip switch controls
are located behind front
panel, through
an opening
below the control
panel.
To access,
remove
front panel. See Fig. 10.
Dip
switches
are accessible
without
opening
the
control
box.
Unit
must
be
powered
OFF
to
effectively
change
their status.
See Table 5 - Dip Switch Functions
for functions
of
each dip switch position.
NOTE"
Configuration
DIP switches
are only read
during
a power
up cycle.
Dipswitch
Fig. 20 - Dip Switches
Fig. 19 - Dipswitch
Location
on Unit
Freeze guard
Setpoint Limit 2
Setpoint Limit 1
Fan CON/CYC
for cooling
Fan CON/CYC
for heating
Wall Thermostat
enable
Electric heat only (for Heat Pumps)
Switches
Table 5--DIP
SWITCH
FUNCTIONS
No,
UP
DOWN
REMARKS
DEFAULT
1
Electric Heat Only
Heat Pump
For Heat Pump unit only.
DOWN
2
Wall Thermostat
Enable
Control Panel Enable
DOWN
3
Fan Continuous
Run for Heating
Fan Cycle for Heat
DOWN
4
Fan Cycle for Cool
Fan Continuous
Run for Cooling
DOWN
5*6
UP*UP
68-75
°F
20-24
°C
UP*DOWN
63-80
°F
18-28°C
DOWN*UP
65-78
°F
19-26 °C
DOWN*DOWN
61-86
°F
16-30
°C
(full range)
Two configurations
(5*6)
combine to select set point
range.
When set point limit set,
display always shows full
range.
DOWN*UP
65-78
°F
19-26
°C
7
Freeze Guard Disable
Freeze Guard Enable
DOWN
Electric
Heating
Only / Emergency
Heat (For
Heat Pump
Units
Only)
This setting is typically
used for Emergency
Heating.
Wall Thermostat
Enable
A wired wall thermostat
can be connected
to the unit.
If it is, this dipswitch
must be moved
to the Wall
Thermostat
Enable
Position,
before
the
wall
thermostat
will begin control.
Heat and Cool Fan CON/CYC
Dip-switches
Allows
the fan to operate
in continuous
or cycle
modes
while the unit is in heating
or cooling
mode
(continuous
or cycle):
CON (Continuous)
Allows
fan to run continuously,
circulating
air even when the
temperature
setting
has been
satisfied.
This
switch
helps
to
maintain
the room temperature
closer to the thermostat
setting.
CYC
(Cycle)
This
setting
allows
the
fan
to cycle
on and
off with
the
compressor
or electric
heater. The fan stops
a short time after
the temperature
setting is satisfied.
Setpoint
Temperature
Limits
Provides
a restricted
range of temperature
control.
Room Freeze
Protection
If unit
senses
a room
temperature
below
40°F
(4.4°C),
the fan motor and electric
strip heat will turn
on and warm the room to 50°F (10°C).
The fan stops
a short time after the temperature
is satisfied.
11