Power source options:
Single phase 120 VAC with neutral wire
Single phase 240 VAC with neutral wire
—48 VDC
Power input receptacles:
120 VAC, 60 Hz NEMA 5-15R to IEC 60320 appliance inlet
240 VAC, 50 Hz country selectable to IEC 60320 appliance inlet
When you install G650s in Japan, use country specific receptacles for 100 and 200 VAC,
50/60 Hz
When you install G650s in Mexico, use country specific receptacles for 127 VAC

Connecting the power cords

!
WARNING:
The AC power cord can connect to a properly rated power distribution unit,
WARNING:
individual AC power receptacles, or to an UPS. Avaya recommends a
rack-mounted UPS.
To connect the power cords:
6. Ensure that the circuit breakers at the AC load center are OFF.
7. Connect the G650 Media Gateway to a UPS or to a "nonswitched" or "always on" electrical
outlet. See
Figure 10: Grounding for multiple G650 Media Gateways
Checking AC power
Each G650 Media Gateway uses at least one auto-ranging (90 to 265 VAC) power supply:
47 to 63 hertz
500 watts output
7.2 amps (90 VAC) or 3.3 amps (200 VAC)
Figure 9: Grounding for one G650 Media Gateway