Verifying ground using an ideal 61-035 Circuit Tester (or equivalent)

To verify ground using an ideal 61-035 Circuit Tester:
1. Plug the circuit tester into the outlet that you want to test.
If the circuit is properly grounded, the yellow and white lights on the tester illuminate.
2. Unplug the tester.
!
WARNING:
If the tester indicates any type of ground fault, your customer must contact a
WARNING:
licensed electrician. DO NOT install the system.
Verifying voltages using a Volt-Ohm Multimeter (VOM) in the U.S. and
countries using 110 to 125 VAC power
!
WARNING:
Hazardous voltages are present during this test. Follow all instructions carefully
WARNING:
when working with AC power line voltages.
Note:
The following example is for North American voltages (110 to 125 VAC). Use the
Note:
appropriate voltages for local power.
To verify voltages using a Volt-Ohm-Multimeter:
3. Ensure that the VOM is set to read Volts AC.
4. Set the VOM to the lowest scale on which you can read 130 VAC.
5. Measure the AC voltages in the following order:
If the voltage readings do not measure the values given, the AC outlet is improperly wired. DO
NOT INSTALL THE SYSTEM. Advise the customer to have a licensed electrician correct the
problem.
You are now ready to power the system.
Installing the G650 Media Gateway
1. Phase to neutral must be 110 to 125 VAC.
2. Neutral to ground must be less than 1 VAC.
3. Phase to ground must be 110 to 125 VAC.
Issue 1 February 2006