CHAPTER 5: CONFIGURING THE SOFTWARE

Transferring a D20 configuration to the D20MX

Prerequisites
Procedure
D20MX HARDWARE USER'S MANUAL
Before you can transfer a D20 device configuration, the following components must be
present:
TM
SGConfig
7.00 or higher installed on the configuration computer.
The D20MX Documentation CD (part number 588-0075/00) installed in a CD/DVD drive
of the configuration computer.
D20 Configuration has been migrated to SGConfig
to the Migration Wizard screencast).
To save time, you may upgrade the firmware definition of your D20 or D200
Configuration to SAN0001 or SAN0002 in ConfigPro. If you choose to take this option,
follow the instructions provided in Section: "Updating D20/D200 configurations to use
the D20MX firmware definition with ConfigPro" on page 75.
To transfer a D20 or D200 device configuration to the D20MX:
1.
Start SGConfig.2
Result: The Welcome to SGConfig screen appears.
2.
Choose the D20MX Factory Default Configuration file, SAG0001-00.7zip or SAG0002-
00.7zip. based on the following criteria:
If transferring a configuration containing B009 versions greater than 310 and
B021 versions greater than 912 use the file SAG0001-00.7zip
If transferring a configuration containing B009 versions less than or equal to 310
and B021 versions less than or equal to 912, use the file SAG0002-00.7zip.
3.
If the SAG0001 or SAG0002 firmware option has already been imported, go to step 4
to open the firmware option. Otherwise perform these steps:
3.1.
Click GE button > Archive > Project > Restore.2
Result: The Restore Project Details window appears.
3.2.
Click ... .
Result: The Choose a File window appears.
3.3.
Navigate to the DVD/CD drive > Configuration Files > SGConfig.
Result: The two files SAG0001-00.zip and SAG0002-00.zip appear in the dialog.
3.4.
Select the appropriate file based on your decision in step 2.
3.5.
Click OK.
Result: On completion a pop-up message appears (e.g. Project 'SAG0001' has
been restored).
3.6.
Click OK.
4.
Open the D20MX Factory Default Configuration SAG0001 or SAG0002: click GE >
Recent Projects > select SAG0001 or SAG0002.
5.
Copy the firmware definition from the factory default configuration to the project
containing the D20 configuration (if you had opted to upgrade the firmware in
ConfigPro, then this step is not necessary):
5.1.
Click the ribbon Configure group > Miscellaneous > Firmware Library.
Result: The Firmware Library window appears with the firmware definition
selected.
5.2.
Click Copy.
Result: The Firmware Information window appears.
5.3.
Set the Project Name in the Copy To region to the project containing the D20
configuration.
GENERAL