Download Image Files To The D20Mx; When To Download; Prerequisites For Image Download - GE D20MX User Manual

Hide thumbs Also See for D20MX:
Table of Contents

Advertisement

CHAPTER 5: CONFIGURING THE SOFTWARE

Download image files to the D20MX

When to download

Prerequisites for image download

Prerequisite for image
download over a
serial link
Prerequisite for image
download over a
network link
D20MX HARDWARE USER'S MANUAL
Table 20: Errors that indicate recovery mode users are active
Error Message
Error: B014USER table missing or no
records.
Login with default user and download
a config with valid B014USER table.
Entering debug mode.
Error: B014USER contains records
with blank usernames.
Login with default user and download
a config with valid B014USER table.
Entering debug mode.
Configuration has been defaulted.
Entering debug mode.
Instances where you may need to download an operating system or application image file
to your D20MX:
When a new version of the operating system or application image has been released.
If the D20MX has performed self-diagnostics and determined that the application
image file is either missing or corrupted.
After maintenance or replacement work that has deleted the application file.
The following items must be available before an application or operating system image file
can be loaded into a D20MX over a serial or network link:
Windows PC with SGConfig version 7 and higher software.
The application firmware file, preferably located on a local hard drive.
This file will be named: appl.out.
Optionally, the operating system image file, preferably located on a local hard drive.
This file will be named: vxWorks.
A NULL modem cable (GE Energy part number 977-0529) connecting the RS-232
connector on the front panel of the D20MX to the serial communications port of a PC
or terminal.
The D20MX module must be installed into a D20 chassis, ready to power-up.
The following item must be available before an application or operating system image file
can be loaded into a D20MX over a serial link:
A NULL modem cable (GE Energy part number 977-0529) connecting the RS-232
connector on the front panel of the D20MX to the serial communications port of a PC
or terminal.
The following item must be available before an application firmware file can be loaded into
a D20MX over the network:
An Ethernet switch and appropriate Ethernet patch cables to connect your PC's
Network Adapter and the D20MX's Ethernet port 1 to the switch.
Remedy
Open the D20MX configuration in SGConfig.
Ensure the B014USER table in the WESMAINT
II+ application (B014-1N) is enabled. Then,
synch the configuration to the D20MX.
Open the D20MX configuration in SGConfig.
Ensure the B014USER table in the WESMAINT
II+ application (B014-1N) contains at least one
record with a non-blank username. Then,
synch the configuration to the D20MX.
Synch a configuration to the D20MX.
GENERAL
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents