Figure 2 shows how to configure the ASD for local/remote operation.
Terminal Function
F terminal: Operating command
R terminal: DeviceNet/Local switching
RR terminal: Operation frequency command
Figure 2. Wiring for Local/Remote Operation
Variable resistor for adjusting
output frequency
Operation command
DeviceNet/Local switch
Parameter setting:
F003 (Command Mode) = 0 (Terminal Block)
F004 (Frequency Mode 1) = 2 (RR)
F112 (Input Terminal 2 (R) Function) = 48 (Remote/Local control)
Operation
R-CC open:
The ASD functions as a follower device on DeviceNet.
R-CC closed:
F-CC: Close to Run
F-CC: Open to Stop
Output frequency is set by the RR signal input.
DeviceNet Module Installation and Operation Manual
10 kΩ
ASD
PP
RR
CCA
F
SW1
R
SOURCE