Features

The external view of the DeviceNet module is shown below.
DeviceNet LED

DeviceNet connector.

Dip switch for setting MAC address and baud rate (see
Baud Rate on pg.
DeviceNet LED indicator (see
DeviceNet Connector
The DeviceNet connector is used to connect DeviceNet network cables to the DeviceNet module card.
The wiring for each terminal on the connector is given below.
Color
Red
White
Silver
Blue
Black
1.
Use shielded wire for the control signal wires.
Use wire size 22 – 16 AWG (0.3 – 1.5 mm 2 ).
2.
3.
Strip 0.28 in. (7 mm) of insulation off the end of the connecting wire.
4.
Use a small slotted (standard) screwdriver to tighten the connector lug screws.
5.
Tighten the connector lug screws. Torque the lug screws to 4.4 – 5.3 in.-lb. (0.5 – 0.6 N•m).
6
indicator
9).
DeviceNet LED Indicator on pg.
Table 1. Pinouts for DeviceNet Connector.
Symbol
V+
Network Power Supply (V+)
CAN_H
Communication Signal (High)
SHIELD
Shield
CAN_L
Communication Signal (Low)
V-
Network Power Supply (V-)
Dip switch
DeviceNet
connector
Setting a MAC ID Number and a Network