32
en | Input and Output Ports
Warning!
!
Operating the input as an analog input between 0.5 V and 5 V might cause abnormal results.
This input state is not defined and might change expected results.
Notice!
i
Reverse configuration is not for use in UL Listed applications.
10.1.2
Automation Link Monitoring (COM3) through CPU Programmable Output
Ports
The output connections on the I/O port have an open collector transistor output that can
activate an external sounder or light if the automation system fails.
Notice!
i
Configure external devices using the specifications listed in the table below. Outputs are not
verified by UL.
Radionics D6615 CPU Terminator Card
Solid state output provides a current sink to
common (-)
Maximum load is 20 mA
Vsat @ 1 mA = 0.5 VDC
Vsat @ 10 mA = 3.0 VDC
Maximum voltage = 30 VDC
Table 10.1: Terminator Card Configuration
2012.11 | 08 | 4998122704
Installation and Operation Guide
Conettix Communications Receiver/
Bosch D6615 CPU Terminator C
Solid State output provides a current sink to
common (-)
Maximum load is 75 mA
Vsat @ 10 mA = 0.5 VDC
Vsat @ 25 mA = 1.0 VDC
Vsat @ 50 mA = 2.5 VDC
Maximum voltage = 30 VDC