Sensor Setup
SENSOR SETUP
IN 2:
DISCH AIR TEMP
The Input 2 sensor (AI2) can be configured for
discharge air temperature (Type III thermistor is the
default), fan status (dry contact), or unused.
• If set for discharge air temperature, the sensor
can be calibrated and changed from the default
Type III thermistor to a Type II. See
Inputs on page
8.
• If set for discharge air temperature, Trend Log
#2 is automatically created and monitors the
discharge air temperature, but it has no effect on
operation.
• If set for fan status and no closed contact is
detected when there is a call for fan operation, a
Fan Fail Alarm is created. See
• If set for unused, built-in applications will not
use AI2, but the input would be available to
custom programming.
Staging Setup
STG DELAY (MINS):
Valve Setup
VALVE SETUP
TYPE:
2–POSITION
ACTION: NRM OPEN
BAC-10000 Series
(Advanced)
Alarms on page
STAGING
3

(Advanced) CB (Control Basic) Programs

CB PROGRAMS
PROG1:
RUNNING
PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE
To halt or load/run the built-in (1–5) and custom
(6–10) Control Basic programs, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
NOTE: If custom Control Basic programs are
installed and a restore to factory settings
is performed, all factory programs are
restarted but all custom Control Basic
programs are halted. Change the state
11.
of each program by loading/running the
program from the CB Programs menu (or
BACstage).
NOTE: If custom Control Basic programs are
installed and set to autorun, whenever the
firmware is updated, ALL (factory and
custom) programs are halted.
If custom Control Basic programs are
installed but NOT set to autorun,
whenever the firmware is updated, factory
programs are restarted but any (manual)
running custom programs are halted at
restart.
Change the state of each custom program
by using the Update Manager or loading/
running each program from the CB
Programs menu (or BACstage).
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
6
PROGRAM #1
SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE
UPDATE MANAGER
NO