location is inadequate. If it does not work with
the test transformer, replace the FlexStat.
• Put another FlexStat on the installed backplate,
and if the second FlexStat functions properly,
replace the first FlexStat.

Configuration and Programming Issues

NOTE: Use the relevant KMC software or app
to perform the following tasks

Application Is Not Correct

NOTE: Select the (AHU, HPU, RTU, or FCU)
application and units BEFORE
changing any other settings. Changing
applications later will reset most
settings back to their defaults. Use
Restore APP in the Advanced menu
or KMC software to verify or change
applications. See
Options) on page
• Select the correct application either through
the menu or through KMC software.
• Select a different model FlexStat with the
necessary options.
NOTE: BAC-19xx36 models support (only)
Air Handling Units and Unit Ventilators
(4-Pipe). BAC-19xx63 models support
(only) Fan Coil Units (2- and 4-Pipe),
Heat Pump Units, and Roof Top Units.

Control Basic Programs Do Not Work

NOTE: The FlexStat has a library of built-
in applications and options that are
configured through the FlexStat's
display. Beyond these standard
configurations, custom changes can
be added to a FlexStat using KMC
software.
NOTE: Control Basic programs 1 through 5 are
used for built-in applications. Programs
6 through 10 are empty and can be
BAC-19xxxx FlexStat Application Guide
Advanced (Menu
4.
used for additional programming. Using
KMC software, a program (1 through
5) can be copied, pasted into a new
program code object (6 through 10),
edited, and run in place of the original.
Make a backup before modifying any
built-in programs!
NOTE: Customized programs are the
responsibility of the user. KMC Controls
does not provide support for such
programs.
• Check that program objects are running and
they have Run on Cold Start selected.
• Check that program objects are not configured
as Out Of Service.
• Check the Control Basic code for errors in
syntax, priority levels, and other issues. For
assistance with Control Basic commands, see
the Help system in the software.
• If firmware has just been upgraded, see
Updating Firmware Issues on page

Configuration Issues

• Check for proper connections between the
controller and software.
• See the help information in the documentation
for the software.
• To restore configuration values to their
factory defaults, change and then restore the
application.

Objects Are Missing

• For missing objects (e.g., objects that have
been accidentally deleted), use KMC software
to create objects.

(Unknown) Password Is Required

• A default Level 2 password is required for initial
configuration. See the
Default Password Technical Bulletin
(TB150716)
by logging into the
18
22.
Conquest Controllers
KMC web
site.
AG200824A